Page 33
vacuum valve and nozzles at the same height
•
One vacuum valve is intended to supply max. 8 vac-
uum nozzles with water.
•
Hose lengths may not exceed 10m on either side.
•
Lay the hose from the vacuum valve to the nozzles
50 mm below the nozzles. Laying the hose further
away leads to reduced output.
•
Never lay the hose from the vacuum valve to the
nozzles above the nozzles because the atomisation
will be too coarse.
•
Use only opaque (black) hosing for water hoses.
»
Secure the vacuum valve with the two appropriate screws.
When connecting the hoses, note the water installation dia-
gram below.
Note:
When the distance between the water installation and the
vacuum valve is greater than 15 m, 10/8 mm plastic hosing
should be used.
water outlet to the
nozzles hose 10/8
mm
water outlet to the
nozzles hose 10/8
mm
water supply from the
filter hose 6/4 mm
control air from control unit
hose 6/4 mm