Are no more than 8 nozzles connected to one vac-
uum valve?
Are the hoses from the atomisation air supply to the
pilot valve no longer than 20 m?
Are all hoses secure and straight in the connectors?
Have the hose lines been laid with at least 50 mm
spare length per meter?
Have the electrical connections been made accord-
ing to the wiring diagram?
Are water and air filters correctly inserted and
secure?
After Nozzle System Startup:
Are the nozzles switched on and off correctly by the
hygrostat (and max. hygrostat)?
Do the nozzles close properly when humidification is
not required?
Are no objects or obstacles being sprayed?