Page 29
•
Distribute the vacuum nozzles as evenly as possible
throughout the space to achieve efficient dispersion
of atomisation.
•
All vacuum nozzles, as well as the vacuum valve,
must be placed at the same height to ensure suffi-
cient, consistent atomisation output.
•
One vacuum valve is intended for use with max. 8
vacuum nozzles and 2x10 hose lengths between the
vacuum valve and the furthest nozzle.
Warning:
Do not install nozzles in the following situations:
•
Nozzles are not to be mounted above machines or
objects susceptible to water damage.
•
Avoid installation right beside an offtake or a dormer
window (or skylight), since the humidity produced
will be immediately removed from the room.
•
Do not install nozzles near a cold air intake.
•
Do not position nozzles directly above regular work
areas, because workers may find the adiabatic cool-
ing effect uncomfortable.
•
The nozzle spray cones cannot overlap. Nozzles
placed opposite each other must have a minimum
separation distance of 10 m to prevent overlapping
spray cones.
•
The spray cone is not to be directed at cold parts of
the building, such as outer walls and windows (dan-
ger of condensation).
•
When the nozzle system is operated using fully dem-
ineralised water, only objects made of plastic or
stainless steel (min. DIN 1.4301) are allowed in the
atomisation area.
Note:
During operation with drinking water, minerals precipitate
during evaporation in the form of dust. To prevent mineral dust,
usage of fully demineralised water is recommended.
Summary of Contents for CU-1
Page 1: ...Atomising Vacuum Nozzle System Manual...
Page 37: ...Page 37 5 4 Example of Installation Fig Example of installation a VN Unit with 4 nozzles...
Page 38: ...Page 38 Fig Example of installation a VN Unit with 8 VN nozzles and 2 vacuum valves...
Page 48: ...Page 48 10 EC Declaration of Conformity...
Page 54: ...Page 54 General 39 Water Installation 39 Wiring Diagram 42...