At temperatures of 20°C ( 5°C), observe the follow-
ing required minimum installation distances for unob-
structed spread of the spray cone at maximum
atomisation output.
Mindestabstände bei 20°C
•
At temperatures over 20°C, the above minimum dis-
tances decrease; at temperatures below 20°C, the
above minimum distances increase.
•
In storage areas, bear in mind that the height of
stocked goods can vary, altering distances to the
nozzles.
•
If you select a higher water pressure for the vacuum
valve (up to 1.1 bar; see section "Output Table"), this
will yield finer atomisation along with reduced atomi-
sation output. This step allows you to reduce mini-
mum installation distances because air absorbs finer
mist more quickly. In this case, you must perform a
specific check to verify that the mist spreads freely at
maximum system air pressure and lowest possible
room temperature!
•
When choosing the installation site, make sure that
nozzles and system components are easily accessi-
ble, e.g. for maintenance. In general, hallways and
driveways are particularly good locations.
•
It is advantageous to install the nozzles close to pre-
heated intake air or a heater.