7.5.3 Proportional Control with Built-In PI-Controller
Upon request, HygroMatik will provide an active sen sor with a
control signal of 0 -10 V DC. Sensors with othe r control signals
can also be used; the control (only available at Comfort or Com-
fort-Plus Control) need only be set to them.
Humidifier Terminals
If other types of active sensors are used Paramter E3 has to be
adjusted:
Humidifier Terminals
Note:
The desired relative humidity value is set at Parameter
P8
(factory setting: P8=50%).
Setting for Sensor Signall
Parameter
U6
E3
0(2) - 10V DC
PI-Control
0 - 10 V
0(4) -20 mA
PI-Control
0 - 20 mA
0 - 140 Ohm
PI-Control
0 - 140 Ohm
Connection: Active Se nsor,
one-cylinder and double- cyl-
inder humidifier; vo ltage out-
put
active sensor
terminal block
Connection: active sensor;
current out put, sin gle-cylin-
der and double cylinder units,
two-wire system