Page 39
6.5 Water Discharge
Warning:
Please pay attention to free a nd non-pressure drain-
age of the wate r! During blo w down up to 0,3 L/s is b eing
drained. For wa ter discharg e, we recommend installation of a
flexible water drain hose. Humidifier and waste water discharge
must be on the same pressure level.
Please note:
•
Do not bend, shorten or lengthen the drain hose.
•
For the discharge line and drain pipe, select materials
temperature-resistant up to 95°C.
Install the water drain system as follows:
•
Install a drain hose 1 1/4 ", 250 -. 1000 mm long, into a
pressure-free outlet according to DIN EN 171 7. Please
ensure that ascending vapor does not condensate on
the humidifier`s housing.
•
Slide the drain hose over the pump discharge hose and
secure to the cabinet drain connection.
A grounding clip is fixed on the inner surface of the cabinet drain
connection.Slide the end of th e pump d rain hose onto this clip.
During blow-down, the grou nding clip will be in direct cont act
with the water and will conduct any residual currents which may
appear away from the cabinet.
There is a 3mm-wide gap between the pump drain hose jacket
and the inner surface of the cabinet dra in connection. If water
collects on the base pla te, it will flow thro ugh this gap into the
drainage system.
Type
Drain Hose
HC 2-27
HS 3-10
1 x 1 1/4"