- 6 -
3.5 Typical arrangement
Note: This arrangement is only an illustrative example.
3.6 Adjusting the bypass
Optimal operation of the heat pump occurs when the cooling gas pressure is 22
r
2 bar.
This pressure can be read on the pressure gauge next to the control heat pump panel. Under these
conditions the water flow through the unit is also optimal.
Note: Operation without a bypass or with improper bypass adjustment may result in sub-optimal
heat pump operation and possibly damage to the heat pump, which renders the warranty null and
void.
Out
In
Heat Pump
Use the following procedure to adjust the
bypass:
x
fully open all three valves
x
slowly close valve 1 until the
water pressure is increased by
approximately 100 to 200 g
x
Close valve 3 approximately
half-way to adjust the gas
pressure in the cooling system
x
If the display shows "ON" or
error code EE3, close step by
step the valve 2, to increase
water flow and stop when the
code disappear.
To pool
From pool
Summary of Contents for Pro+ 22T
Page 1: ...Swimming Pool Heat Pump User and Service manual EnglishƔFrenchƔDutchƔGermanƔRussianƔPolish ...
Page 20: ... 18 ...
Page 24: ... 22 9 Exploded Diagram and Maintenance 9 1 Exploded Diagram Model 5 kw ...
Page 46: ... 44 7 3 Comment savoir les états actuels ...
Page 50: ... 48 9 Schéma eclaté et entretien 9 1 Schéma eclaté Modèle 5 kw ...
Page 66: ... 64 5 2 ZWEMBAD WARMTEPOMP BEDRADING SCHEMA Hydro Pro 13 18 ...
Page 72: ... 70 7 2 Hoe de huidige status te weten te komen ...
Page 76: ... 74 9 Open geklapt diagram en onderhoud 9 1 Open geklapt diagram Model 5 kw ...
Page 98: ... 96 7 2 Den aktuellen Status abrufen ...
Page 102: ... 100 9 Explosionszeichnung und Wartung 9 1 Explosionszeichnung Modell 5 kw ...
Page 124: ... 122 7 2 Ʉɚɤ ɭɡɧɚɬɶ ɬɟɤɭɳɢɣ ɫɬɚɬɭɫ ...
Page 128: ... 126 9 ɉɨɞɪɨɛɧɚɹ ɞɢɚɝɪɚɦɦɚ ɢ ɨɛɫɥɭɠɢɜɚɧɢɟ 9 1 ɉɨɞɪɨɛɧɚɹ ɞɢɚɝɪɚɦɦɚ Ɇɨɞɟɥɶ 5 ɤȼɬ ...
Page 150: ... 148 7 2 Odczytywanie bieĪącego stanu urządzenia ...
Page 154: ... 152 9 Schemat budowy pompy 9 1 Widok urządzenia rozebranego Model 5 kw ...