8.2 Other Malfunctions and Solutions (No display on LED wire controller)
Malfunctions
Observing
Reasons
Solution
LED wire controller
no display.
No power supply
Check cable and circuit
breaker if it is connected
LED wire controller.
displays the actual time.
Heat pump under standby
status
Startup heat pump to run.
Heat pump is
not running
LED wire controller
displays the actual
water temperature.
1. Water temperature is
reaching to setting value, HP under
constant temperature status.
2. Heat pump just starts to run.
3. Under defrosting.
1. Verify water temperature
setting.
2. Startup heat pump after
a few minutes.
3. LED wire controller
should display
"Defrosting".
Water
temperature is
cooling when
HP runs under
heating mode
LED wire controller
displays actual water
temperature and no error
code displays.
1. Choose the wrong mode.
2. Figures show defects.
3. Controller defect.
1. Adjust the mode to
proper running
2. Replace the defect LED
wire controller, and then
check the status after
changing the running
mode, verifying the water
inlet and outlet
temperature.
3. Replace or repair the
heat pump unit
Short running
LED displays actual water
temperature, no error code
displays.
1. Fan NO running.
2. Air ventilation is not enough.
3. Refrigerant is not enough.
1. Check the cable
connections between the
motor and fan, if
necessary, it should be
replaced.
2. Check the location of
heat pump unit, and
eliminate all obstacles to
make good air ventilation.
3 Replace or repair the
heat pump unit.
water stains
Water stains on heat pump
unit.
1. Concreting.
2. Water leakage.
1. No action.
2. Check the titanium heat
exchanger carefully if it is
any defect.
Too much ice
on evaporator
Too much ice on
evaporator.
1. Check the location of
heat pump unit, and
eliminate all obstacles to
make good air ventilation.
2. Replace or repair the
heat pump unit.
Summary of Contents for Pro+ 22T
Page 1: ...Swimming Pool Heat Pump User and Service manual EnglishƔFrenchƔDutchƔGermanƔRussianƔPolish ...
Page 20: ... 18 ...
Page 24: ... 22 9 Exploded Diagram and Maintenance 9 1 Exploded Diagram Model 5 kw ...
Page 46: ... 44 7 3 Comment savoir les états actuels ...
Page 50: ... 48 9 Schéma eclaté et entretien 9 1 Schéma eclaté Modèle 5 kw ...
Page 66: ... 64 5 2 ZWEMBAD WARMTEPOMP BEDRADING SCHEMA Hydro Pro 13 18 ...
Page 72: ... 70 7 2 Hoe de huidige status te weten te komen ...
Page 76: ... 74 9 Open geklapt diagram en onderhoud 9 1 Open geklapt diagram Model 5 kw ...
Page 98: ... 96 7 2 Den aktuellen Status abrufen ...
Page 102: ... 100 9 Explosionszeichnung und Wartung 9 1 Explosionszeichnung Modell 5 kw ...
Page 124: ... 122 7 2 Ʉɚɤ ɭɡɧɚɬɶ ɬɟɤɭɳɢɣ ɫɬɚɬɭɫ ...
Page 128: ... 126 9 ɉɨɞɪɨɛɧɚɹ ɞɢɚɝɪɚɦɦɚ ɢ ɨɛɫɥɭɠɢɜɚɧɢɟ 9 1 ɉɨɞɪɨɛɧɚɹ ɞɢɚɝɪɚɦɦɚ Ɇɨɞɟɥɶ 5 ɤȼɬ ...
Page 150: ... 148 7 2 Odczytywanie bieĪącego stanu urządzenia ...
Page 154: ... 152 9 Schemat budowy pompy 9 1 Widok urządzenia rozebranego Model 5 kw ...