- 19 -
Parameter Meaning
Range
Default Remarks
0
To set the entering water temp.
under cooling mode
8-35
ć
28
ć
Adjustable
1
To set the entering water temp.
under heating mode
15-35
ć
28
ć
Adjustable
2
Entry into defrosting time period
30-90MIN
40MIN
Adjustable
3
Terms of Entry defrosting function
-30
ć
to0
ć
-7
ć
Adjustable
4
Terms of Exit defrosting
2 to 30
ć
13
ć
Adjustable
5
Time of Exit defrosting
1 to 12MIN
12MIN
Adjustable
6
Mode: 0 Cool 1 Heat and Cool 2
Heat and cool+ auxiliary elec.
Heating 3 Heat
0-3 1(Heat
and
Cool)
Adjustable
7
Mode selection of Electronic
expansion valve
0-1 1(auto)
Adjustable
8
Superheat for heating target
-15
ć
-15
ć
3
ć
Adjustable
9
Superheat for cooling target
-15
ć
-15
ć
10
ć
Adjustable
A
Manual adjustment steps of
electronic expansion valve
18-94 70
Adjustable
B
Inlet water temperature
-9-99
ć
ʳ
Exact testing by value
C
Outlet water temperature
-9-99
ć
ʳ
Exact testing by value
D
Condenser temperature under
heating mode
-9-99
ć
ʳ
Exact testing by value
E
Gas return temperature
-9-99
ć
ʳ
Exact testing by value
F
Ambient temperature
-9-99
ć
ʳ
Exact testing by value
G
Condenser temperature under
Cooling mode
-9-99
ć
ʳ
Exact testing by value
H
Actual steps of electronic
expansion valve
N*5
ʳ
Exact testing by value
Remarks:
(1) When HP stop running in 30 seconds, water pump will shut off automatically
(2) LED wire controller can operate the water pump after connected additional cable to the pump device in
the position of “PUMP” terminal accurately.
(3) It is necessary to put an extra 3-phase transfer device for 3 phase water pump.
Summary of Contents for Pro+ 22T
Page 1: ...Swimming Pool Heat Pump User and Service manual EnglishƔFrenchƔDutchƔGermanƔRussianƔPolish ...
Page 20: ... 18 ...
Page 24: ... 22 9 Exploded Diagram and Maintenance 9 1 Exploded Diagram Model 5 kw ...
Page 46: ... 44 7 3 Comment savoir les états actuels ...
Page 50: ... 48 9 Schéma eclaté et entretien 9 1 Schéma eclaté Modèle 5 kw ...
Page 66: ... 64 5 2 ZWEMBAD WARMTEPOMP BEDRADING SCHEMA Hydro Pro 13 18 ...
Page 72: ... 70 7 2 Hoe de huidige status te weten te komen ...
Page 76: ... 74 9 Open geklapt diagram en onderhoud 9 1 Open geklapt diagram Model 5 kw ...
Page 98: ... 96 7 2 Den aktuellen Status abrufen ...
Page 102: ... 100 9 Explosionszeichnung und Wartung 9 1 Explosionszeichnung Modell 5 kw ...
Page 124: ... 122 7 2 Ʉɚɤ ɭɡɧɚɬɶ ɬɟɤɭɳɢɣ ɫɬɚɬɭɫ ...
Page 128: ... 126 9 ɉɨɞɪɨɛɧɚɹ ɞɢɚɝɪɚɦɦɚ ɢ ɨɛɫɥɭɠɢɜɚɧɢɟ 9 1 ɉɨɞɪɨɛɧɚɹ ɞɢɚɝɪɚɦɦɚ Ɇɨɞɟɥɶ 5 ɤȼɬ ...
Page 150: ... 148 7 2 Odczytywanie bieĪącego stanu urządzenia ...
Page 154: ... 152 9 Schemat budowy pompy 9 1 Widok urządzenia rozebranego Model 5 kw ...