58
any
block
4.
Change
a
new
exhaust
temp.
sensor
d6
‐
TH3
5.
Check
whether
the
current
ambient
temp.
and
water
temp.
are
beyond
the
running
temp.
of
the
machine
EE
06
Controller
failure
1.
Signal
is
not
well
connected
or
damaged
2.
Controller
failure
1.
Stop
the
power
supply
and
restart.
2.
Re
‐
connect
the
signal
wire
or
replace
a
new
one
3.
Replace
a
new
controller
EE
07
Compressor
current
protection
1.
The
compressor
current
is
too
large
instantaneously
2.
Wrong
connection
for
compressor
phase
sequence
3.
Compressor
accumulations
of
liquid
and
oil
lead
to
the
current
becomes
larger
4.
Compressor
or
driver
board
damaged
5.
The
water
flow
is
abnormal
6.
Power
fluctuations
within
a
short
time
1.Check
if
the
power
in
the
normal
range
2.
Check
the
compressor
3.
Check
the
compressor
phase
4.
Check
the
phase
sequence
connection
5.
Check
the
waterway
system
and
filtration
pump
6.
Check
mains
power
input
EE
08
Communication
failure
between
controller
and
main
board
1.
Signal
wire
is
not
well
connected
or
damaged
2.
Controller
failure
3.
Driving
failure
1.
Stop
the
power
supply
and
restart.
Re
‐
connect
the
signal
wire
or
replace
a
new
one
2.
Check
the
controller
or
replace
a
new
one
3.
Check
the
driving
system
or
update
it.
4.
Check
the
driving
system
or
update
it.
EE
09
Communication
failure
between
Main
control
board
and
Driving
board
1.
Poor
connection
of
communication
wire
2.
PCB
failure
3.
The
wire
is
damaged
1.
Stop
the
power
supply
and
restart.
2.
Reconnect
the
communication
wire
or
replace
a
new
one
3.
Check
the
wirings
according
to
the
electric
diagram
4.
Replace
a
new
PCB
EE
10
VDC
voltage
too
high
protection
1.
Line
voltage
is
too
high
2.
Driver
board
is
damaged.
1.
Check
whether
the
power
supply
is
normal
2.
Change
driver
board
or
main
board
EE
11
IPM
module
protection
1.
Data
mistake
2.
Wrong
compressor
phase
connection
3.
Compressor
liquid
and
oil
accumulation
lead
to
the
current
becomes
larger
4.
Compressor
or
driver
board
damaged
1.
Program
error,
turn
off
electricity
supply
and
restart
after
3
minutes
2.
Change
driver
board
3.
Check
compressor
sequence
connection
Summary of Contents for 5
Page 8: ...7 2 Wymiary mm Model Inverter 5 Inverter 7 Inverter 10 Model Inverter 13 Inverter 18 ...
Page 31: ...30 ...
Page 35: ...34 Naciśnij i przytrzymaj przez 5 sekund aż zacznie migać ...
Page 45: ...44 2 Dimension mm Model Inverter 5 Inverter 7 Inverter 10 Model Inverter 13 Inverter 18 ...
Page 70: ...69 3 Opertion of Alsova Pro APP Press and hold 5 second until is flashing ...
Page 80: ...79 Model Inverter 13 Inverter 18 ...
Page 107: ...10 3 Die Hauptschnittstelle Wechselrichter 5 Sekunden gedrückt halten bis blinkt ...
Page 111: ...110 überprüfen ...
Page 116: ......
Page 117: ......
Page 118: ......
Page 119: ...A0111HYIELR3204 ...