The temperature must rise above 23 degrees to trigger the alarm but
fall below
22 degrees
before the logger checks-in with a return-to-normal event.
The Alpha field can be used to provide some noise reduction in special
circumstances but should normally be left as 0.
Provided the logger is transferring data to Timeview correctly, there is no more
alarm setup required on the logger.
Once you have configured alarms on the logger, trigger a dial-out to Timeview so
that the logger alarm configuration information is transferred. See