Alarms
As well as the regular calls to transfer data,
alarms
can be configured on the
Hydro-Logic
®
Flexi Logger 100 so that certain site conditions are detected and
trigger a data transfer to the telemetry server. Alarm information from site is then
forwarded from Timeview to individuals or groups.
Harvest software is used for configuring alarms. There is also some setup
required on Timeview.
Both the logger and Timeview configuration must be
correct for alarms to work properly.
Logger alarm configuration
The Alarms check box (1) is on the sensor tab:
Once selected, you get the alarm config box:
Set point and alarm condition
The are up to 4 alarms for every channel. The
Alarm Condition
field sets how
the logger should react when the
Set Point
is crossed. Here, we want the logger
to contact Timeview whenever the temperature exceeds 23 degrees, and when it
returns to normal.
Hysteresis
This is used to prevent multiple alarms if the sensor value is near the set point.
This parameter is shown as a grey bar on the plot: