Connecting the sensors
SensorMonitoring Unit - SMU
en(us)
Page 32 / 100
BeWa SMU1200 3854281 V2.0x en(us) 2013-08-20
2013-08-20
Connecting the sensors
Before connection, check the model/type designation or sensor imprint of the
SMU in connection with the sensors that you plan to use. The sensors are
connected through the unit plugs on the underside of the SMU.
The analog outputs and/or the switching outputs of the sensors are looped
through and are available for further use at the 8-pin or 5-pin outlet socket.
The HSI bus signals are supplied via the HSI interface G.
The SMU expects a digital HSI bus signal from all sensors.
NOTICE
Contact of individual wires leads to short circuits
Connected sensors are destroyed
►
Insulate and secure any open cable ends not required against
inadvertent reciprocal contact
NOTICE
Same HSI bus address of the sensors
SMU1200 functions incorrectly
►
Take note of different HSI bus addresses
NOTICE
Incorrect Hardwareindex of CS1000 / AS1000 sensors
The SMU functions incorrectly
►
Only use CS1000 with a Hardwareindex
≥
C.
(Type plate -> Serial No: xxx
C
xxxxxx or Date: xx/10
C
)
►
Only use AS1000 with a serial No:
≥
607B001647 with Firmware
≥
V01.03