UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
3 Installation
Issue 02 (2017-02-25)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
107
Figure 3-70
Connecting signal cables
The number and colors of signal cables in
----End
3.2.8 Routing Cables (UPS5000-E-300K-SMT)
Context
The basic rule for routing cables is: from inside out and from bottom up.
After routing cables, use firestop putty to fill in the gap between the cables and the cabinet.
Procedure
Step 1
Ensure the maintenance bypass switch is OFF. Open the front door and remove the cover
from the power distribution subrack, as shown in