UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
5 Operations
Issue 02 (2017-02-25)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
236
Figure 5-44
Clearing faults
Step 3
Check that the EPO alarm is cleared by viewing active alarms. If the system bypass input is
normal, the UPS transfers to bypass mode.
Viewing active alarms on the LCD
Choose
System Info
>
Alarms
and tap
Active Alarms
to check that the EPO alarm is
cleared.
Figure 5-45
Active alarms
Viewing active alarms on the WebUI
In a web browser, enter the UPS IP address and select a display language. Enter a user
name and password, and click
Login
to open the homepage. Choose
Monitoring
>
Active Alarms
to check that the EPO alarm is cleared. If the bypass input is normal, the
UPS transfers to bypass mode.