UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
5 Operations
Issue 02 (2017-02-25)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
224
If an incorrect password is entered three consecutive times, the account will be logged out for 5
minutes.
Step 3
On the
Maintenance
screen, tap
Battery Maint.
, as shown in
Step 4
Tap
Start
on the right of
Shallow Dis. Test
to start a shallow discharge test, as shown in
Figure 5-26
Starting a shallow discharge test
When the battery test is complete, the test data is used as common test data. Record the data obtained
from the latest five tests.
Tap
Stop
next to
Shallow Dis. Test
in any of the following cases:
The battery discharge capacity reaches the specified value (10%–50%, 20% by default).
The discharge voltage reaches the warning threshold (calculated in real time).
The load ratio fluctuation exceeds 10%.
An alarm is generated.
----End
5.6.3 Capacity Test
Context
Before a capacity test, ensure that: