background image

UPS5000-E-(50 kVA-300 kVA) 
User Manual (50 kVA Power Modules) 

3 Installation 

 

Issue 02 (2017-02-25) 

Huawei Proprietary and Confidential                                     

Copyright © Huawei Technologies Co., Ltd. 

106 

 

Figure 3-69

 

Connecting power cables 

 

 

 

For details about how to connect the battery neutral wire, see 

Figure 3-36

 in 

3.2.5.1 Routing Cables from 

the Top

.   

 

Single mains 

For single mains, the copper bars between the mains and bypass input terminals do not 
need to be removed, and bypass input cables do not need to be connected. 

Step 5

 

Route the signal cables on the left sideof subracks along the left side of the cabinet and the 
cables on the right side of subracks along the right side of the cabinet, and then bind the 
cables to the cabinet, as shown i

Figure 3-70

. 

Summary of Contents for UPS5000-E Series

Page 1: ...UPS5000 E 50 kVA 300 kVA User Manual 50 kVA Power Modules Issue 02 Date 2017 02 25 HUAWEI TECHNOLOGIES CO LTD ...

Page 2: ... Huawei and the customer All or part of the products services and features described in this document may not be within the purchase scope or the usage scope Unless otherwise specified in the contract all statements information and recommendations in this document are provided AS IS without warranties guarantees or representations of any kind either express or implied The information in this docum...

Page 3: ...upport engineers System engineers Hardware installation engineers Commissioning engineers Data configuration engineers Maintenance engineers Symbol Conventions The symbols that may be found in this document are defined as follows Symbol Description Indicates an imminently hazardous situation which if not avoided will result in death or serious injury Indicates a potentially hazardous situation whi...

Page 4: ...attention to important information best practices and tips NOTE is used to address information not related to personal injury equipment damage and environment deterioration Change History Updates between document issues are cumulative Therefore the latest document issue contains all updates made in previous versions Issue 01 2017 02 25 Updated the voltage and current data of the monitoring interfa...

Page 5: ...tion 12 2 2 Working Principle 13 2 2 1 Conceptual Diagram 13 2 2 2 Working Modes 14 2 2 2 1 Normal Mode 14 2 2 2 2 Bypass Mode 15 2 2 2 3 Battery Mode 16 2 2 2 4 Maintenance Bypass Mode 17 2 2 2 5 ECO Mode 18 2 3 Product Introduction 19 2 3 1 Structure 19 2 3 2 Power Module 24 2 3 3 Bypass Module 25 2 3 4 Control Module 27 2 3 4 1 Overview 27 2 3 4 2 ECM 27 2 3 4 3 Dry Contact Card 29 2 3 4 4 Opti...

Page 6: ...t 64 3 2 3 3 Connecting an Ambient T H Sensor 65 3 2 3 4 Connecting the BCB box 66 3 2 3 5 Connecting the BBB box 66 3 2 3 6 Installing a Battery Grounding Failure Detector 66 3 2 3 7 Connecting the iBAT 68 3 2 4 UPS Cable Connection Reference 69 3 2 5 Routing Cables UPS5000 E 200K SM 71 3 2 5 1 Routing Cables from the Top 71 3 2 5 2 Routing Cables from the Bottom 78 3 2 6 Routing Cables UPS5000 E...

Page 7: ...2 2 2 Real time Data Page 182 4 2 2 3 Param Settings Page 182 4 2 2 4 Comm Config Page 183 4 2 2 5 CIM Parameters 183 4 2 2 6 Control Page 184 4 2 3 Query Page 184 4 2 3 1 Historical Alarms Page 184 4 2 3 2 Logs Page 185 4 2 4 Config Page 185 4 2 4 1 User Management 185 4 2 4 2 Site Config Page 186 4 2 4 3 RCCMD 188 4 2 4 4 Managing the UPS by Using the NMS Complying with RFC1628 Standard 197 4 2 ...

Page 8: ... 12 2 WebUI 240 6 Routine Maintenance 242 6 1 UPS Maintenance 242 6 1 1 Monthly Maintenance 242 6 1 2 Quarterly Maintenance 243 6 1 3 Annual Maintenance 243 6 2 Battery Maintenance 244 6 2 1 Precautions for Battery Maintenance 245 6 2 2 Monthly Maintenance 245 6 2 3 Quarterly Maintenance 246 6 2 4 Annual Maintenance 247 7 Troubleshooting 248 8 Technical Specifications 250 8 1 Physical Specificatio...

Page 9: ...0 E 50 kVA 300 kVA User Manual 50 kVA Power Modules Contents Issue 02 2017 02 25 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd viii C Alarm List 276 D Acronyms and Abbreviations 289 ...

Page 10: ...tain Huawei equipment Follow the precautions and special safety instructions provided by Huawei when operating Huawei products Huawei will not be liable for any consequences that are caused due to violations regarding general safety regulations and equipment design production and usage safety standards Declaration Huawei does not take responsibilities for the following situations Operation under s...

Page 11: ...re Allowed to install operate and maintain the equipment Allowed to remove safety facilities and inspect the equipment Allowed to replace or change the devices or components including software Operation personnel must report faults or errors that might cause serious safety issues to related owners This product should be installed and used according to the installation and technical specification r...

Page 12: ...s where adequate care has to be taken to ensure personal safety discuss with the manufacturer in advance about the applicability settings management and maintenance of the UPS which require special considerations during design Device Safety Before operation ensure that the device is firmly anchored to the floor or other solid objects such as a wall or an installation rack Ensure ventilation vents ...

Page 13: ...n a damp environment ensure that the device is dry When water is found in the rack or the rack is damp switch off the power supply immediately High Leakage Current Ground a device before powering it on Otherwise personal injury or device damage may occur If a high leakage current tag is attached to the panel of the device ground the protective ground terminal on the device enclosure before connect...

Page 14: ...se backfeed protection paste labels on the external bypass input circuit breakers informing that the circuit is connected to the UPS Disconnect the device from the UPS before performing operations on the circuit Electrostatic Discharge Static electricity generated by human bodies may damage the electrostatic sensitive components on boards for example the large scale integrated LSI circuits Wear a ...

Page 15: ...t that has flammable air can cause extreme danger Strictly obey the operating environmental requirements specified in related use manuals when using or storing the device Keep the UPS away from the following environments Places where the temperature and humidity are beyond the range of 0 40 C and 0 95 RH respectively Places in direct sunlight or near heat sources Places subject to vibrations or sh...

Page 16: ... boards and ultimately damaging the circuit boards Short circuits caused by incorrect operations may cause serious injuries due to high power of batteries Do not reversely connect positive and negative battery terminals Use batteries of the specified type Otherwise the batteries may be damaged Check battery connections periodically to ensure that all screws are securely tightened Install or store ...

Page 17: ...cuits may cause personal injury The high transient current generated by a short circuit may release a surge of power and cause a fire To avoid battery short circuits do not maintain batteries while they are in use Harmful Gas Do not use unsealed lead acid batteries Lead acid batteries emit flammable gas Therefore place and secure lead acid batteries horizontally to prevent fire or corrosion Store ...

Page 18: ...ectrolyte wash the exposed area with clean water immediately and seek medical advice if the situation is serious 1 5 Mechanical Safety Moving Sharp Objects Wear protective gloves when moving sharp objects Moving Heavy Objects Perform operations in accordance with all instructional symbols on the device Take caution to avoid injury when moving heavy objects When moving or lifting a device hold the ...

Page 19: ...ions may damage the cable sheathing To ensure cable safety comply with the following requirements Cables can be laid or installed only when the temperature is higher than 0 C 32 F Handle cables with caution especially at lower temperatures Before laying out cables that have been stored in temperatures lower than 0 C 32 F move the cables to an environment that is at the requisite ambient temperatur...

Page 20: ... 25 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 11 behind the air exhaust vent of the cabinet The air exhaust vent should not be blocked by any object Before connecting a cable ensure that the cable and cable label to be used meet the actual installation requirements ...

Page 21: ...ils Figure 2 1 UPS model number Table 2 1 Model number details No Item Description 1 Product category UPS 2 UPS family 5000 3 UPS subcategory E series 4 Output capacity 200K 200 kVA 300K 300 kVA 5 Configuration type SM standard configuration FM full configuration 6 Cable routing Routed from the top only the UPS5000 E 320K SMT model contains T This document describes the following UPS models UPS500...

Page 22: ... a cable entry cabinet is configured The UPS5000 E 300K SM supports cable routing from the bottom The UPS5000 E 300K SMT supports cable routing from the top 2 2 Working Principle indicates an input mode indicates the energy flow direction 2 2 1 Conceptual Diagram The UPS5000 is an online UPS with a modular design that facilitates maintenance and capacity expansion All modules are under intelligent...

Page 23: ...e 2 2 UPS conceptual diagram 2 2 2 Working Modes 2 2 2 1 Normal Mode In normal mode the rectifier converts AC power into DC power then the inverter converts DC power into high precision AC outputs The conversions protect loads from interference such as input harmonics glitches and voltage transients Figure 2 3 shows a conceptual diagram of the UPS working in normal mode ...

Page 24: ...in normal mode 2 2 2 2 Bypass Mode The UPS automatically transfers to bypass mode upon detecting power module overtemperature overload or other faults that may cause the inverter to shut down The bypass power supply is not protected by the UPS which means it may be affected by mains outage and incorrect AC voltage or frequency Figure 2 4 shows a conceptual diagram of the UPS working in bypass mode...

Page 25: ...ght Huawei Technologies Co Ltd 16 Figure 2 4 UPS conceptual diagram in bypass mode 2 2 2 3 Battery Mode If the AC input voltage is not normal the UPS transfers to battery mode to obtain power from batteries The inverter then converts the power into AC outputs Figure 2 5 shows a conceptual diagram of the UPS working in battery mode ...

Page 26: ...gies Co Ltd 17 Figure 2 5 UPS conceptual diagram in battery mode 2 2 2 4 Maintenance Bypass Mode In maintenance bypass mode the current flows through maintenance bypass circuits instead of the power module or bypass module UPS maintenance can be performed in this mode Figure 2 6 shows a conceptual diagram of the UPS working in maintenance bypass mode ...

Page 27: ... be configured on the LCD or web user interface WebUI In ECO mode when the bypass input voltage is within the ECO voltage range the static bypass switch turns on and the bypass supplies power When the bypass input voltage is outside the ECO voltage range the UPS transfers from bypass mode to normal mode In bypass mode or normal mode the rectifier keeps working and charging the batteries using a ch...

Page 28: ...n ECO mode Manual startup is required to ensure that the inverter is in standby state and the power flow has reached the inverter 2 3 Product Introduction 2 3 1 Structure Figure 2 8 shows the front view of the UPS5000 E 200K SM Figure 2 9 shows the front view of the UPS5000 E 200K FM Figure 2 10 shows the front view of the UPS5000 E 300K SM Figure 2 11 shows the front view of the UPS5000 E 300K SM...

Page 29: ...25 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 20 Figure 2 8 UPS5000 E 200K SM front view with the door open 1 Power modules 2 Bypass module 3 Control module 4 Power distribution subrack cover 5 Filler panels 6 Monitor display unit 7 Maintenance bypass switch ...

Page 30: ...idential Copyright Huawei Technologies Co Ltd 21 Figure 2 9 UPS5000 E 200K FM front view with the door open 1 Power distribution subrack cover 2 Bypass input switch 3 Maintenance bypass switch 4 Mains input switch 5 Output switch 6 Control module 7 Bypass module 8 Power modules 9 Monitor display unit 10 Filler panels ...

Page 31: ...5 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 22 Figure 2 10 UPS5000 E 300K SM front view with the door open 1 Power modules 2 Bypass module 3 Control module 4 Power distribution subrack cover 5 Monitor display unit 6 Filler panels 7 Maintenance bypass switch ...

Page 32: ...5 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 23 Figure 2 11 UPS5000 E 300K SMT front view with the door open 1 Power distribution subrack cover 2 Maintenance bypass switch 3 Control module 4 Bypass module 5 Power modules 6 Monitor display unit 7 Filler panels ...

Page 33: ...indicator 4 Fault indicator 5 Ready switch 6 Output port 7 Input port Functions The power module consists of a power factor correction PFC rectifier and inverter The rectifier performs AC DC or DC DC conversion on the mains and battery inputs and stabilizes the bus voltage The inverter converts DC inputs into AC sine wave outputs Specifications Dimensions H x W x D 130 mm x 442 mm x 620 mm Weight ...

Page 34: ...t Huawei Technologies Co Ltd 25 2 3 3 Bypass Module Appearance Figure 2 13 shows a bypass module of a 200 kVA UPS Figure 2 13 Bypass module 1 Positioning lock 2 Cold start button 3 Run indicator 4 Alarm indicator 5 Fault indicator 6 Ready switch 7 Signal port 8 Input and output ports Figure 2 14 shows a bypass module of a 300 kVA UPS ...

Page 35: ...d output ports 9 Crowbar Functions The bypass module supplies power in the following cases If the UPS is set to ECO mode and the bypass voltage is within the specified range the UPS works in bypass mode If the power module overload times out the UPS transfers to bypass mode Both the active and standby ECMs are abnormal The system fails to run properly and transfers to bypass mode A manual operatio...

Page 36: ...into this subrack Figure 2 15 shows the signal panel on the control module Figure 2 15 Signal panel on the control module 1 Ground terminal 2 Parallel port 1 3 BSC port 1 4 ECM 1 ready switch 5 Indicators for ECM 1 6 Parallel port 2 7 BSC port 2 8 ECM 2 ready switch 9 Indicators for ECM 2 10 Dry contact card 11 Dry contacts 12 MDU port 13 RS485 port 14 Fast Ethernet FE port 15 COM2 port 16 COM1 po...

Page 37: ...f the UPSs in the shape of a ring N UPSs require N parallel cables so that at least two parallel cables are connected to each UPS which improves reliability BSC The BSC port is used in a dual bus system to synchronize output frequencies and phases between UPS systems ensuring that two buses can switch with each other For a single UPS the parallel cable is not needed Table 2 3 Indicator description...

Page 38: ... power off EPO Figure 2 17 shows control signal ports on the dry contact card Figure 2 17 Dry contact card Table 2 4 describes the ports on the dry contact card Table 2 4 Ports on the dry contact card Silk Screen Description Status Initial Status BTG Port for detecting battery grounding faults Connected battery grounding fault Disconnected no battery grounding fault Disconnected 0V Port for signal...

Page 39: ...ort is disconnected from the EPO_12V port EPO is triggered Connected EPO_12V 12 V SWITCH STATUS_ OUT Port for monitoring the UPS output circuit breaker Connected circuit breaker ON Disconnected circuit breaker OFF Connected SWITCH STATUS_ 0V Port for signal ground SWITCH STATUS_ MT Port for monitoring the maintenance circuit breaker Disconnected circuit breaker ON Connected circuit breaker OFF Dis...

Page 40: ...e signal input ports For details see the UPS5000 Dry Contact Extended Card User Manual 03021RKN 2 3 4 6 Monitoring Interface Card The FE port resembles the RS485 port Follow the silk screen when connecting communications cables as if the RS485 port is mistaken for the FE port during cable connection the WebUI cannot be connected and MDU communication fails Conversely if the FE port is mistaken for...

Page 41: ...NO DO_2 is used to output alarms and indicates minor alarms by default It can be set to indicate critical alarms bypass mode battery mode or low battery voltage COM DO_3 NO DO_3 is used to output alarms and indicates bypass mode by default It can be set to indicate critical alarms minor alarms battery mode or low battery voltage COM DO_4 NO DO_4 is used to output alarms and indicates battery mode ...

Page 42: ...icatio ns port RS485 Connects to a northbound network management device or a third party network management device over two wires Signal cables must be double insulated twisted cables If the cable length is 25 50 m the cross sectional area must be 0 5 1 5 mm2 RS485 cables and FE cables must be shielded cables Figure 2 19 and Figure 2 20 are recommended wiring methods for DO ports Figure 2 19 Wirin...

Page 43: ...017 02 25 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 34 Figure 2 21 COM1 pins Table 2 6 COM1 pin definition Pin Description 1 GND 2 N A 3 RS485 4 RS485 5 N A 6 12V_PORT Figure 2 22 and Table 2 7 describe the COM2 pin definitions Figure 2 22 COM2 pins ...

Page 44: ...right Huawei Technologies Co Ltd 35 Table 2 7 COM2 pin definition Pin Description 1 RS485 2 RS485 3 N A 4 RS485 5 RS485 6 GND 7 CANH0 8 CANL0 Figure 2 23 and Table 2 8 describe the RS485 pin definitions Figure 2 23 RS485 pins Table 2 8 RS485 pin definition Pin Description 1 RS485_T 2 RS485_T 3 N A 4 RS485_R 5 RS485_R 6 GND 7 N A ...

Page 45: ...ht loads Due to its modular design the power will be redundant when loads are light N X parallel system where N is the number of requisite UPSs connected in parallel and X is the number of redundant UPSs An N X parallel system supplies power to important loads in small and medium sized equipment rooms It features high reliability and powerful transient overload capacity 1 N X 4 1 N 4 0 X 3 For exa...

Page 46: ...rgy control modules ECMs on each UPS are connected over parallel cables The parallel connections synchronize the UPS outputs to supply power to loads If one UPS fails the other UPSs continue supplying power to loads Figure 2 24 shows a conceptual diagram of an N X parallel system Figure 2 24 Conceptual diagram of an N X parallel system 2 4 3 Dual Bus System A dual bus system consists of two indepe...

Page 47: ...on BCB box PDC 0250DC0384BX A PDC 0400DC0384BX A PDC 0630DC0384BX A PDU8000 0125DCV8 BXA001 PDU8000 0250DCV8 BXA001 PDU8000 0400DCV8 BXA001 PDU8000 0630DCV8 BXA001 PDU8000 0800DCV8 BXA001 Controls the connection between battery strings and the UPS Provides overload protection short circuit protection and remote trip control Battery bus bar BBB box PDU8000 0630DCV8 BGA001 PDU8000 1250DCV8 BGA001 PD...

Page 48: ...acks cannot be used simultaneously Antiseismic kit N A Reinforces the cabinet so that the cabinet meets the requirements of 9 degree seismic fortification intensity IP21 component N A Prevents water from dropping into the cabinet protecting the cabinet to IP21 Top outlet kit N A If you need to install the cabinet against a wall install a top outlet kit to meet heat dissipation requirements Dry con...

Page 49: ... 5 m 10 m 15 m Connects UPSs in parallel BSC cable 5 m 10 m 15 m 60 m Transmits bus synchronization signals in a dual bus system Top air flow cabinet N A Used to ensure heat dissipation and allows the UPS to be installed against a wall The ECM extended subrack does not support onsite installation If you require this optional component inform Huawei when you purchase the UPS Huawei installs it befo...

Page 50: ...ear the weight of the UPS5000 E batteries and battery racks The weight of batteries and battery racks depends on the UPS configuration for the site Table 3 1 lists the UPS5000 E weight Table 3 1 UPS weight Model Capacity Weight UPS5000 E 200K SM 50 kVA 224 kg 100 kVA 256 kg 150 kVA 288 kg 200 kVA 320 kg UPS5000 E 200K FM 50 kVA 254 kg 100 kVA 286 kg 150 kVA 318 kg 200 kVA 350 kg UPS5000 E 300K SM ...

Page 51: ...ation Issue 02 2017 02 25 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 42 Figure 3 1 shows the installation dimensions for the UPS5000 E 200K SM and UPS5000 E 300K SM SMT Figure 3 2 shows the installation dimensions for the UPS5000 E 200K FM ...

Page 52: ...ation Issue 02 2017 02 25 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 43 Figure 3 1 UPS5000 E 200K SM and UPS5000 E 300K SM SMT dimensions unit mm 1 Front door 2 Foot 3 Caster 4 Base 5 Rear panel 6 Base installation hole 7 Beam 8 Side beam ...

Page 53: ...les 3 Installation Issue 02 2017 02 25 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 44 Figure 3 2 UPS5000 E 200K FM dimensions unit mm 1 Front door 2 Foot 3 Caster 4 Base 5 Rear panel 6 Base installation hole 7 Beam 8 Side beam ...

Page 54: ...regulated lead acid batteries VRLA batteries are 20 30 C Operating temperatures higher than 30 C shorten the battery lifespan and operating temperatures lower than 20 C reduce the battery backup time 3 1 1 3 Installation Clearances Reserve the following clearances around the cabinet to facilitate operations and ventilation Reserve at least 800 mm from the front and rear of the cabinet Reserve at l...

Page 55: ...stallation Table 3 2 Tools and meters Tools and Meters Electric pallet truck Manual pallet truck Ladder Rubber mallet Hammer drill and drill bit Φ16 Hand held electric drill Alloy hole saw Heat gun Diagonal pliers Crimping tools Wire stripper Electric hydraulic pliers Clamp meter Multimeter Cable tie Level instrument Polyvinyl chloride PVC insulation tape Cotton cloth Label Electrician s knife Ele...

Page 56: ...cated tools required see the corresponding component manuals Prepare tools based on site requirements 3 1 3 Preparing Power Cables The UPS can generate large leakage currents A circuit breaker that provides leakage current protection is not recommended If multiple UPSs are to be connected in parallel input and output power cables for each UPS should have the same length and specifications The TN C...

Page 57: ...2 x 4 x 150 L2 L3 N PE 25 35 70 95 120 150 Byp ass inpu t Bypass input current A 76 152 228 304 380 456 Recommen ded cross sectio nal area mm2 L1 4 x 25 4 x 70 2 x 4 x 70 2 x 4 x 95 2 x 4 x 120 2 x 4 x 150 L2 L3 N PE 25 35 70 95 120 150 Out put Output current A 76 152 228 304 380 456 Recommen ded cross sectio nal area mm2 U 4 x 25 4 x 70 2 x 4 x 70 2 x 4 x 95 2 x 4 x 120 2 x 4 x 150 V W N PE 25 35...

Page 58: ...ut share a power source configure input power cables as mains input power cables In addition cables listed in Table 3 3 apply only to the following conditions 200 kVA The cables are installed along the wall or on the floor IEC 60364 5 52 C standards 300 kVA The cables are routed over a ladder or bracket in a single layer IEC60364 5 52 F standards The ambient temperature is 30 C The AC voltage loss...

Page 59: ... m Battery input Crimped OT terminals M12 13 5 mm 60 mm 46 N m Output Crimped OT terminals M10 10 5 mm 40 mm 26 N m PE Crimped OT terminals M10 10 5 mm 30 mm 26 N m Table 3 6 lists the requirements for power cable terminals of the UPS5000 E 300K SM SMT Table 3 6 Power cable terminal requirements for the 300 kVA cabinet Port Descript ion Recommende d Connection Method Bolt Specificat ions Bolt Hole...

Page 60: ...nput circuit breaker T1N160 TMD R160 FFC 3P ABB recommende d when the short circuit current where the switch is located is less than 36 kVA Bypass input circuit breaker T1N160 TMD R100 FFC 3P Downstream output circuit breaker T1N160 TMD R100 FFC 3P 100 kVA Mains input circuit breaker T3N250 TMD R250 FF 3P Bypass input circuit breaker T1N160 TMD R160 FFC 3P Downstream output circuit breaker T1N160 ...

Page 61: ...h circuit breakers must not exceed the recommended specifications The circuit breaker selection principle is to protect loads and cables and the cascading principle is to realize specific protection 3 1 4 Unpacking and Checking Context To prevent the UPS from falling over secure it to a pallet truck using ropes before moving it To prevent shocks or falls move the UPS gently After placing the UPS i...

Page 62: ...chnologies Co Ltd 53 Figure 3 4 Removing binding tapes Step 4 Remove packing materials as shown in Figure 3 5 Figure 3 5 Removing packing materials Step 5 Remove the plastic bag and take out the fittings box Step 6 Check that the UPS is intact 1 Visually inspect the UPS appearance for shipping damage If it is damaged notify the carrier immediately ...

Page 63: ...ei office immediately Step 7 Remove the L shaped bracket that secures the cabinet and the pallet and secure the sliding plate to the pallet by using the two M12 screws that were removed as shown in Figure 3 6 Figure 3 6 Removing the L shaped bracket Tighten the two screws in step 2 in Figure 3 6 Otherwise the slide plate may move when the UPS is removed 10 screws need to be removed from each L sha...

Page 64: ...sing the leveling feet Step 9 Push the cabinet along the sliding plate to the floor End 3 2 Installing a Single UPS 3 2 1 Installing the Cabinet Secured Installation Step 1 Determine the position for installing the cabinet Mark mounting holes for the UPS based on the following figures Figure 3 8 for the UPS5000 E 200K SM and UPS5000 E 300K SM SMT Figure 3 9 for the UPS5000 E 200K FM ...

Page 65: ...r Manual 50 kVA Power Modules 3 Installation Issue 02 2017 02 25 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 56 Figure 3 8 UPS5000 E 200K SM and UPS5000 E 300K SM SMT mounting holes positioning unit mm ...

Page 66: ...000 E 200K FM mounting holes positioning unit mm Step 2 Use a hammer drill to drill four holes for installing expansion bolts and then install four expansion bolts in the holes Figure 3 10 shows the composition of an expansion bolt and Figure 3 11 shows how to install an expansion bolt Figure 3 10 Expansion bolt composition 1 M12 bolt 2 Spring washer 3 Flat washer 4 Expansion sleeve ...

Page 67: ...ound by using a hammer drill The hole depth is 52 mm to 60 mm 2 Partially tighten the expansion bolt and vertically insert it into the hole Hit the expansion bolt using a rubber mallet until the expansion sleeve is fully inserted into the hole 3 Partially tighten the expansion bolt 4 Remove the bolt spring washer and flat washer Step 3 Move the cabinet over its castors to the installation position...

Page 68: ... 02 25 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 59 Figure 3 12 Removing the rear panel Step 6 Remove the four rubber plugs from the bottom of the cabinet two at the front and two at the rear as shown in Figure 3 13 Skip this step for the UPS5000 E 200K FM ...

Page 69: ...oprietary and Confidential Copyright Huawei Technologies Co Ltd 60 Figure 3 13 Removing rubber plugs Step 7 Insert four M12 x 115 expansion bolts into the expansion bolt holes in the floor and tighten the expansion bolts in the direction as shown in Figure 3 14 Figure 3 14 Tightening expansion bolts End ...

Page 70: ...tep 2 Check whether the bottom of the cabinet is horizontal by using a level If the cabinet is not level adjust the leveling feet End 3 2 2 Installing Batteries Context Before installing batteries read through the battery safety precautions obtain the delivered battery installation guide and install batteries as instructed Place the batteries in a correct way to prevent vibrations and shocks Insta...

Page 71: ...g off template Determine the installation positions for the antiseismic kits based on the delivered marking off template and mark mounting holes Without a marking off template Mark mounting holes based on the following figure Figure 3 16 Antiseismic kit mounting hole positions Step 2 Complete Step 2 to Step 6 in section Secured Installation under 3 2 1 Installing the Cabinet Step 3 Secure two anti...

Page 72: ...arking off template use eight M6x20 and four M12 screws Figure 3 18 Securing the antiseismic kits to the cabinet without a marking off template Step 4 Reinstall the rear panel Step 5 Adjust the cabinet position so that the expansion bolt holes are aligned with the eight holes at the bottom of the cabinet Step 6 Secure antiseismic kits to the floor at both the front and rear of the cabinet by using...

Page 73: ...stalling an IP21 Component Procedure Step 1 Install leveling feet at the bottom of the IP21 component with two long feet on the front and two short feet at the rear Refer to the front and back silk screens on the surface of the IP21 component Select the mounting holes for leveling feet based on the cabinet width onsite Figure 3 20 Installing leveling feet Step 2 Secure the IP21 component to the to...

Page 74: ...nent End 3 2 3 3 Connecting an Ambient T H Sensor Procedure Step 1 Connect the RJ11 port on the ambient temperature and humidity sensor T H sensor to the COM1 port on the UPS monitoring interface card For details see UPS Ambient Temperature and Humidity Sensor User Manual 02310NBS Figure 3 22 Connecting a UPS and an ambient T H sensor The ambient T H sensor can be used as a battery temperature sen...

Page 75: ...250 2000 DCV8 BGA001 BBB Box User Manual 3 2 3 6 Installing a Battery Grounding Failure Detector Procedure Step 1 Install a battery grounding failure detector For the installation method see UPS5000 Battery Grounding Failure Detector User Manual Figure 3 23 shows the position for a battery grounding failure detector in a UPS5000 E 200K SM Figure 3 24 shows the position for a battery grounding fail...

Page 76: ...rietary and Confidential Copyright Huawei Technologies Co Ltd 67 Figure 3 24 Position of a battery grounding failure detector in a UPS5000 E 200K FM 1 Battery grounding failure detector Figure 3 25 Position of a battery grounding failure detector in a UPS5000 E 300K SM 1 Battery grounding failure detector ...

Page 77: ...s Co Ltd 68 Figure 3 26 Position of a battery grounding failure detector in a UPS5000 E 300K SMT 1 Battery grounding failure detector End 3 2 3 7 Connecting the iBAT Procedure Step 1 Connect the COM_OUT port on the CIM of the iBAT to the COM2 port on the monitoring interface card For details see the document delivered with the iBAT Figure 3 27 COM2 port End ...

Page 78: ... cable to the copper bar to which the cable will be connected determine the cable length and label the cable Mark a line where the cable is to be cut Mark a line where the cable is to be stripped and an OT DT terminal is to be crimped Step 3 Pull the cable that has been marked out of the cabinet cut the cable from the marked position and strip the cable and crimp an OT DT terminal at the other mar...

Page 79: ...User Manual 50 kVA Power Modules 3 Installation Issue 02 2017 02 25 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 70 Figure 3 28 UPS cable connection Step 5 Clean foreign matter inside the cabinet End ...

Page 80: ...es from the Top Context Route cables for the UPS from inside out and from bottom up After routing cables use firestop putty to fill in the gap between the cables and the cabinet Procedure Step 1 Ensure the maintenance bypass switch is OFF Open the front door and remove the cover from the power distribution subrack as shown in Figure 3 29 The positioning of the copper bars is shown in Figure 3 30 F...

Page 81: ...ut terminals N 2 Mains input terminals 1L1 1L3 N 3 Maintenance bypass switch 4 Bypass input terminals 2L1 2L3 N 5 Output terminals U V W and N Step 2 Determine the cabling mode Remove small covers or drill holes on the large cover to route cables based on site conditions Remove the cable cover from the top of the cabinet for cable routing Remove the small covers from the top of the cabinet as show...

Page 82: ...moving the cable covers from the top of the cabinet Drill holes for routing cables Remove the cable cover for signal cables from the cabinet and drill holes on the middle large cover based on the number and diameter of cables as shown in Figure 3 32 Remove the cover and then drill holes If holes are drilled for routing cables attach grommet strips to the hole edges to protect cables ...

Page 83: ...nual 50 kVA Power Modules 3 Installation Issue 02 2017 02 25 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 74 Figure 3 32 Drilling holes on the top cover Step 3 Connect ground cables as shown in Figure 3 33 ...

Page 84: ...sed on Table 3 3 and the site requirements The following figure is for reference only Prepare the OT terminals onsite to ensure that the length of the copper wire is the same as that of the part of the OT terminal that covers the conductor Figure 3 33 Ground cable In the figure the wiring terminal with a circle is the primary wiring terminal that connects to the ground cable Step 4 Route power cab...

Page 85: ...s Co Ltd 76 Figure 3 34 Removing copper bars Figure 3 35 shows cables routed from the top by removing small covers as an example Figure 3 35 Top cabling Route a neutral wire from the middle of the positive and negative battery strings The battery neutral wire is routed from the middle of positive and negative battery strings each consisting of 20 batteries ...

Page 86: ... mains For single mains the copper bars between the mains and bypass input terminals do not need to be removed and bypass input cables do not need to be connected Step 5 Route the signal cables on the left sideof subracks along the left side of the cabinet and the cables on the right side of subracks along the right side of the cabinet and then bind the cables to the cabinet as shown in Figure 3 3...

Page 87: ...lation Issue 02 2017 02 25 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 78 Figure 3 37 Connecting signal cables The number and colors of signal cables in Figure 3 37 are for reference only End 3 2 5 2 Routing Cables from the Bottom Context ...

Page 88: ...3 29 Figure 3 30 shows the positions of copper bars Step 2 Determine the cabling mode Remove small covers for routing cables Remove the cable cover for signal cables and remove small covers from the bottom based on site requirements as shown in Figure 3 38 Figure 3 38 Removing small covers from the bottom of the cabinet Drill holes into the large cover for routing cables a Remove all the cable cov...

Page 89: ...logies Co Ltd 80 Figure 3 39 Hole positions The quantity of holes in the above figure is for reference only If holes are drilled for routing cables attach grommet strips on the hole edges to protect cables c Reinstall the removed two small covers on the holes at the rear bottom of the cabinet as shown in Figure 3 40 Figure 3 40 Installing small covers ...

Page 90: ...bles as shown in Figure 3 41 Figure 3 41 Ground cable connection In the figure the wiring terminal with a circle is the primary wiring terminal that connects to the ground cable Step 4 Route power cables Dual mains Remove the copper bars between mains and bypass input terminals as shown in Figure 3 34 Figure 3 42 shows power cables routed from the bottom by removing small covers as an example ...

Page 91: ...e mains For single mains the copper bars between the mains and bypass input terminals do not need to be removed and bypass input cables do not need to be connected Step 5 Route the signal cables on the left sideof subracks along the left side of the cabinet and the cables on the right side of subracks along the right side of the cabinet and then bind the cables to the cabinet as shown in Figure 3 ...

Page 92: ...s in Figure 3 43 are for reference only End 3 2 6 Routing Cables UPS5000 E 200K FM 3 2 6 1 Routing Cables from the Top Context Route cables for the UPS from inside out and from bottom up After routing cables use firestop putty to fill in the gap between the cables and the cabinet Procedure Step 1 Open the front door and remove the cover from the power distribution subrack as shown in Figure 3 44 F...

Page 93: ...UPS5000 E 50 kVA 300 kVA User Manual 50 kVA Power Modules 3 Installation Issue 02 2017 02 25 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 84 Figure 3 44 Removing the cover ...

Page 94: ...85 Figure 3 45 Copper bar positions 1 Mains input terminals 1L1 1L3 N 2 Bypass input terminals 2L1 2L3 N 3 Battery input terminals N 4 Output terminals U V W and N Step 2 Determine the cabling mode Remove small covers for routing cables Take out the cable cover for signal cables and remove small covers from the top based on site requirements as shown in Figure 3 46 ...

Page 95: ...86 Figure 3 46 Removing small covers from the top of the cabinet Drill holes into the large cover for routing cables a Remove the cable cover for signal cables and small covers from the top b Remove the two large covers from the rear top of the cabinet drill holes into them and install them to the positions where the small covers were placed as shown in Figure 3 47 ...

Page 96: ...rietary and Confidential Copyright Huawei Technologies Co Ltd 87 Figure 3 47 Hole positions The quantity of holes in the above figure is for reference only If holes are drilled for routing cables attach grommet strips to the hole edges to protect cables Step 3 Connect ground cables as shown in Figure 3 48 ...

Page 97: ...les Determine the actual number of ground cables based on Table 3 3 and the site requirements The following figure is for reference only Prepare the OT terminals onsite to ensure that the length of the copper wire is the same as that of the part of the OT terminal that covers the conductor Figure 3 48 Ground cable connection Step 4 Route power cables Dual mains Remove the copper bars between mains...

Page 98: ...etary and Confidential Copyright Huawei Technologies Co Ltd 89 Figure 3 49 Removing copper bars Figure 3 50 shows the cables routed from the top of the cabinet Figure 3 50 Top cabling 1 Mains input terminals 1L1 1L3 N 2 Battery input terminals N 3 Bypass input terminals 2L1 2L3 N 4 Output terminals U V W N ...

Page 99: ...nd bypass input terminals do not need to be removed and bypass input cables do not need to be connected Step 5 Route the signal cables on the left sideof subracks along the left side of the cabinet and the cables on the right side of subracks along the right side of the cabinet and then bind the cables to the cabinet as shown in Figure 3 51 Figure 3 51 Connecting signal cables The number and color...

Page 100: ...firestop putty to fill in the gap between the cables and the cabinet after routing cables and checking cable connections Procedure Step 1 Optional Determine the installation position for the cable entry cabinet and draw mounting holes in the installation position based on drawings Figure 3 52 Mounting holes for the cable entry cabinet Step 2 Remove the right and rear covers from the UPS cabinet an...

Page 101: ...Ltd 92 Step 4 Install equipotential plate mounting kits on the same horizontal plane of the UPS cabinet and cable entry cabinet The recommended installation positions are shown in the following figure Figure 3 53 Equipotential plate mounting kit Step 5 Place the cable entry cabinet on the right of the UPS cabinet Step 6 Install the front and rear connecting kits ...

Page 102: ...prietary and Confidential Copyright Huawei Technologies Co Ltd 93 Figure 3 54 Connecting kit Step 7 Optional Secure the cable entry cabinet to the ground For details about how to secure the cable entry cabinet see Secured Installation in 3 2 1 Installing the Cabinet Step 8 Install an equipotential plate ...

Page 103: ...ables Remove a certain number of small covers from the bottom of the cable entry cabinet based on the actual cable conditions Figure 3 56 Removing small covers Drill holes on the large cover for routing cables a Remove all small covers from the bottom of the cable entry cabinet b Remove the two large covers from the bottom of the cable entry cabinet drill holes into them based on site requirements...

Page 104: ...i Proprietary and Confidential Copyright Huawei Technologies Co Ltd 95 Figure 3 57 Removing large covers The quantity of holes in the above figure is for reference only If holes are drilled for routing cables attach grommet strips on the hole edges to protect cables Step 10 Connect the ground cables ...

Page 105: ...00 kVA User Manual 50 kVA Power Modules 3 Installation Issue 02 2017 02 25 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 96 Figure 3 58 Connecting the ground cables Step 11 Connect power cables ...

Page 106: ...PS5000 E 50 kVA 300 kVA User Manual 50 kVA Power Modules 3 Installation Issue 02 2017 02 25 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 97 Figure 3 59 Connecting power cables ...

Page 107: ... kVA User Manual 50 kVA Power Modules 3 Installation Issue 02 2017 02 25 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 98 Step 12 Remove the signal cable trough cover from the cable entry cabinet ...

Page 108: ...VA User Manual 50 kVA Power Modules 3 Installation Issue 02 2017 02 25 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 99 Figure 3 60 Removing the cable trough cover Step 13 Connect the signal cable ...

Page 109: ... right of the cable entry cabinet and install other covers in the original positions End 3 2 7 Routing Cables UPS5000 E 300K SM Context Route cables for the UPS from inside out and from bottom up After routing cables use firestop putty to fill in the gap between the cables and the cabinet Procedure Step 1 Open the front door and remove the cover from the power distribution subrack as shown in Figu...

Page 110: ...ver Figure 3 63 Copper bar positions 1 Battery input terminals N 2 Bypass input terminals 2L1 2L3 N 3 Mains input terminals 1L1 1L3 N 4 Output terminals U V W and N 5 Maintenance bypass switch Step 2 Determine the cabling mode Remove small covers for routing cables Take out the cable cover for signal cables and remove small covers from the bottom based on site requirements as shown in Figure 3 64 ...

Page 111: ... Ltd 102 Figure 3 64 Removing small covers from the bottom of the cabinet Drill holes into the large cover for routing cables a Remove all small covers from the bottom of the cabinet b Remove the two large covers from the rear bottom of the cabinet drill holes into them and install them to the positions where the small covers were placed as shown in Figure 3 65 ...

Page 112: ...ogies Co Ltd 103 Figure 3 65 Hole positions The quantity of holes in the above figure is for reference only If holes are drilled for routing cables attach grommet strips to the hole edges to protect cables c Re install the removed two small covers on the holes at the rear bottom of the cabinet as shown in Figure 3 66 Figure 3 66 Installing small covers ...

Page 113: ...wei Technologies Co Ltd 104 Step 3 Connect ground cables as shown in Figure 3 67 Figure 3 67 Grounding In the figure the wiring terminal with a circle is the primary wiring terminal that connects to the ground cable Step 4 Route power cables Dual mains Remove the copper bars between the mains and bypass input terminals as shown in Figure 3 68 ...

Page 114: ...50 kVA Power Modules 3 Installation Issue 02 2017 02 25 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 105 Figure 3 68 Removing copper bars Figure 3 69 shows the power cables routed from the bottom of the cabinet ...

Page 115: ...e see Figure 3 36 in 3 2 5 1 Routing Cables from the Top Single mains For single mains the copper bars between the mains and bypass input terminals do not need to be removed and bypass input cables do not need to be connected Step 5 Route the signal cables on the left sideof subracks along the left side of the cabinet and the cables on the right side of subracks along the right side of the cabinet...

Page 116: ... signal cables in Figure 3 70 are for reference only End 3 2 8 Routing Cables UPS5000 E 300K SMT Context The basic rule for routing cables is from inside out and from bottom up After routing cables use firestop putty to fill in the gap between the cables and the cabinet Procedure Step 1 Ensure the maintenance bypass switch is OFF Open the front door and remove the cover from the power distribution...

Page 117: ... Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 108 Figure 3 71 Removing the cover Figure 3 72 Copper bar positions 1 Mains input terminals 1L1 1L3 N 2 Bypass input terminals 2L1 2L3 N 3 Battery input terminals N 4 Maintenance bypass switch 5 Output terminals U V W N ...

Page 118: ...r the power cables and signal cables from the cabinet drill holes into the cable cover attach grommet strips to the hole edges for cable protection and reinstall the cable cover for the power cables as shown in Figure 3 73 Figure 3 73 Removing the cable cover from the top of the cabinet The quantity of holes in the above figure is for reference only Step 3 Connect ground cables as shown in Figure ...

Page 119: ...nd Confidential Copyright Huawei Technologies Co Ltd 110 Figure 3 74 Grounding In the figure the wiring terminal with a circle is the primary wiring terminal that connects to the ground cable Step 4 Route power cables Dual mains Remove the copper bar between mains and bypass input terminals as shown in Figure 3 75 ...

Page 120: ...nual 50 kVA Power Modules 3 Installation Issue 02 2017 02 25 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 111 Figure 3 75 Removing copper bars Figure 3 76 shows the cables routed from the top of the cabinet ...

Page 121: ...etails about how to connect the battery neutral wire see Figure 3 36 in 3 2 5 1 Routing Cables from the Top Single mains For single mains the copper bar between the mains and bypass input terminals do not need to be removed and bypass input cables do not need to be connected Step 5 Route signal cables Bind cables to the cabinet Figure 3 77 shows the signal cables routed from the top of the cabinet...

Page 122: ...e If the cable is required the recommended cable is 22 AWG Equip the EPO switch with a protective cover to prevent misoperations and cover the cable with protective tubing Triggering EPO will shut down the rectifier inverter charger and static bypass but does not disconnect the UPS mains input To power off the UPS completely open the front end input switch when triggering EPO Connect the requisite...

Page 123: ...emove the jumper between EPO_NC and EPO_12V before connection When the EPO switch is turned off EPO is triggered When the EPO switch is in the NO state ensure that the jumper is connected between EPO_NC and EPO_12V When the EPO switch is turned on EPO is triggered 3 2 10 Connecting Communications Cables Procedure Step 1 Connect the external network management device to the RS485 port Step 2 Connec...

Page 124: ...installation methods For details see 3 2 Installing a Single UPS Step 2 Unscrew the connecting kits at the front and rear of the cabinet align them with the reserved holes that can connect the two UPSs and then use screws to tighten the connecting kits to the cabinet according to the following figures Figure 3 80 shows the connection point for the UPS5000 E 200K SM and UPS5000 E 300K SM SMT Figure...

Page 125: ...K SM is used as an example The parallel power cables for different UPS models can be connected in a similar way Procedure Step 1 Ground each UPS in a parallel system separately and connect power cables and battery cables according 3 2 Installing a Single UPS Step 2 Based on the site configurations select a parallel connection method to connect cables for the parallel system Figure 3 82 shows a typ...

Page 126: ... 25 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 117 This document uses the number of oblique lines to indicate the number of power cables of the same type Figure 3 82 Conceptual diagram of a 1 1 parallel system Connect power cables according to port silk screen ...

Page 127: ...d 118 Figure 3 83 Cable connections for a 1 1 parallel system 1 Mains input power cables 2 Bypass input power cables 3 Battery cables 4 Output power cables Figure 3 84 shows a typical conceptual diagram for a dual bus system consisting of two UPS systems and Figure 3 85 show the cable connections for this system Figure 3 84 Conceptual diagram of a dual bus system ...

Page 128: ...ecting Signal Cables Context A maximum of four UPS5000 E 200K SM FMs and UPS5000 E 300K SM SMTs can be connected in parallel Cable connection principles for two UPSs connected in parallel are the same as those for four UPSs connected in parallel The following describes how to connect cables for four UPSs connected in parallel Procedure Step 1 Connect the parallel ports on the UPSs using parallel c...

Page 129: ... 3 86 Topology diagram of an N X parallel system Figure 3 87 shows only control modules Each control module represents a single UPS Figure 3 87 Connecting signal cables in a parallel system consisting of four UPSs In a dual bus system you need to connect cables to BSC ports on the UPSs Figure 3 88 shows the cable connections for a dual bus system containing two master systems ...

Page 130: ...for each UPS by referring to 2 3 4 Control Module End 3 4 Installation Verification Table 3 9 lists check items If the check results of listed items 10 and 11 in Table 3 9 do not meet the acceptance criteria the UPS may be damaged Table 3 9 Installation checklist No Item Acceptance Criteria 01 Consistency between system configurations and delivery configurations The system configurations including...

Page 131: ...ar The resistancemust be less than 1 ohm 08 Distances between cable ties Distances between cable ties are the same recommended distance is 30 cm and no burr exists 09 Correct cable connections Cables are properly connected according to wiring diagrams 10 Live wire and neutral wire connections Input and output live wires and neutral wires are correctly connected Mains input terminals 1L1 1L2 1L3 an...

Page 132: ...ve dust 14 Copper busbar short circuit Copper busbars are confirmed as being open circuited using a multimeter or an insulation resistance tester 1 In the scenarios where holes are drilled for routing cables or covers are removed for routing cables after routing cables and checking cable connections use firestop putty to fill in the gap between the cables and the cabinet 2 After verifying the inst...

Page 133: ...on the front door of the cabinet allows for general UPS operations parameter setting viewing of running status and alarms and so on The MDU provides a status indicator and an LCD touchscreen as shown in Figure 4 1 Figure 4 1 MDU 1 Status indicator 2 LCD touchscreen Touch the LCD screen firmly because it is an industrial resistive touchscreen It is recommended that you use your fingernails for accu...

Page 134: ...dicator Table 4 1 Status indicator Status Color Meaning On Red A critical alarm has been generated and the buzzer sounds continuously Yellow A minor alarm has been generated and the buzzer buzzes at 2 Hz Green The UPS is running properly Off N A The MDU is powered off The indicator on the LCD panel is yellow when the bypass supplies power in non ECO mode 4 1 2 LCD Menu 4 1 2 1 Menu Hierarchy Figur...

Page 135: ...tartup User interfaces displayed in this document correspond to the monitor display module MDU version V100R003C01 and are for reference only The Settings Wizard screen is displayed when the UPS is started for the first time or when the UPS restarts after restoring factory settings Parameters including Language Time Network Param and System Param can be set on the Settings Wizard of the MDU as sho...

Page 136: ... Confidential Copyright Huawei Technologies Co Ltd 127 Figure 4 4 Settings Wizard 4 1 2 3 Main Menu The LCD screen is divided into three parts status bar alarm bar and information area Figure 4 5 numerically labels functions of the default main screen and Table 4 2 describes these functions Figure 4 5 Main Menu screen ...

Page 137: ...the number of active alarms based on severity Tap the alarm icon area to open the active alarm page 3 Informatio n area Displays the power flow as well as key information such as load and battery information Tap the Bypass Mains Battery and Load icons to view details Table 4 3 describes the functions of common buttons Table 4 3 Functions of common buttons Button Function Returns to the main screen...

Page 138: ... Module Data Screen On the System Info tap the UPS picture On the Module Data screen select a module to view its running data indicates the selected module as shown in Figure 4 7 Figure 4 7 Module Data screen 4 1 3 2 Runn Info Screen On the System Info screen tap to access the Runn Info screen On this screen AC Output UPS Load Mains Input and Bypass Input can be queried as shown in Figure 4 8 and ...

Page 139: ...re 4 9 Runn Info screen 2 On the System Info Settings Advanced Param screen if the Current equal detection is set to Enable and the number of inverter modules is greater than or equal to 2 the Mod Cur Eql Data is displayed on the Runn Info screen On the System Info Settings CIM Param Basic Param screen if the Number of battery strings is not 0 the Battery Detailed Data is displayed on the Runn Inf...

Page 140: ...awei Technologies Co Ltd 131 AC Output Figure 4 10 AC Output screen Item Description Phase voltage V AC output phase voltage Line voltage V AC output line voltage Phase current A AC output phase current Frequency Hz AC output frequency Power factor Proportion of output active power to output apparent power UPS Load Figure 4 11 UPS Load screen ...

Page 141: ...quare root of the difference between the square of output apparent power and the square of output active power Load ratio Load ratio of each phase on the UPS that is proportion of actual power to rated power Crest factor Proportion of the peak value of load current to the valid value Mains Input Figure 4 12 Mains Input screen Item Description Phase voltage V Mains input phase voltage Line voltage ...

Page 142: ...133 Bypass Input Figure 4 13 Bypass Input screen Item Description Phase voltage V Bypass input phase voltage Line voltage V Bypass input line voltage Phase current A Bypass input phase current Frequency Hz Bypass input frequency Power factor Proportion of the bypass input active power to the bypass input apparent power Battery Status Figure 4 14 Battery Status screen ...

Page 143: ...rent of the battery string the current is when batteries are being charged and when discharged Temperatu re C Battery operating temperature A battery sensor is required If the sensor is not installed NA is displayed Backup time min Battery backup time estimated at the current load Remaining cap Remaining battery capacity SOH State of health Total Runtime Figure 4 15 Total Runtime screen Item Descr...

Page 144: ...e value takes 1 Environment Data Figure 4 16 Environment Data screen Item Description Ambient temperat ure C Temperature measured by the ambient temperature and humidity sensor The sensor needs to be installed If the sensor is not installed the data uploaded by the bypass module is displayed Ambient humid Humidity measured by the ambient temperature and humidity sensor If the sensor is not install...

Page 145: ...s Co Ltd 136 Figure 4 17 Mod Cur Eql Data screen Battery Detailed Data Figure 4 18 shows the Battery Detailed Data screen Figure 4 18 Battery Detailed Data screen This screen details battery string data and single battery data in each battery string The N in String N Battery Data should be less than or equal to 4 Figure 4 19 shows the Batt String Data screen ...

Page 146: ...ry string Figure 4 20 shows the String N Battery Data screen Figure 4 20 String N Battery Data screen This screen displays the temperature voltage internal resistance current SOC and SOH of a single battery in the battery string and the mapping between the CIM and BIM 4 1 3 3 Alarms Screen Tap on the System Info screen to enter the Alarms screen On the Alarms screen active alarms and historical al...

Page 147: ...ntial Copyright Huawei Technologies Co Ltd 138 Figure 4 21 Alarms screen Active Alarms Figure 4 22 shows the Active Alarms screen Figure 4 22 Active Alarms screen This screen displays alarm information including the severity name ID location and generation time Historical Alarms Figure 4 23 shows the Historical Alarms screen ...

Page 148: ... including the severity name ID location generation time and clear time Buzzer Off Two buzzer menus are available Buzzer On If this selection is enabled when a critical alarm a minor alarm or a certain warning is generated the buzzer is activated Buzzer Off If this selection is enabled the buzzer is muted If the buzzer is enabled Buzzer Off is displayed on the operation screen Figure 4 24 shows th...

Page 149: ...er name and password and tap Figure 4 25 Clear Faults screen For details about default user names preset passwords and user rights see Table 4 5 If an incorrect password is entered three consecutive times the account will be locked out for 5 minutes 4 1 3 4 Settings Screen On the System Info screen tap If you have not logged in a login screen is displayed as shown in Figure 4 26 Figure 4 26 Login ...

Page 150: ...user names and preset passwords and describes the permission of the default users If you enter incorrect passwords for three consecutive times you will be locked out for 5 minutes Figure 4 27 Settings screen 1 Figure 4 28 Settings screen 2 Basic Settings Set the date and time correctly Incorrect time display in running and alarm information would lead to analysis errors during maintenance or repai...

Page 151: ...uding English Chinese Spanish Dutch French German Italian Polish Portuguese Russian Swedish and Turkish The default language is English Password The preset password is 000001 The password can be changed password complexity check If the password complexity check is disabled the user password is required to be a string of six to eight digits If the password complexity check is enabled the password i...

Page 152: ...bnet as the PC IP address Perform the bitwise AND operation for the UPS IP address and the PC IP address with the subnet mask respectively If the operation results are the same the two IP addresses are in the same subnet AND operation rule 1 AND 1 1 1 AND 0 0 0 AND 1 0 0 AND 0 0 That is when the corresponding bits are both 1 the result is 1 In other cases the result is 0 Table 4 4 BitwiseAND opera...

Page 153: ...s 192 168 0 1 NAT mapping NAT means network address translation If it is set to Disable an internal IP address cannot be accessed from the Internet RS485 com baud rate Baud rate depends on the network management conditions Figure 4 32 Communication screen 2 Item Description RS485 com address Set an address that ranges from 1 to 254 for this port Parity mode Verify the validity of RS485 communicati...

Page 154: ...s set on the LCD is the same as that set for the DIP switch Otherwise communication cannot be implemented Amb temp humid sensors Start addr of amb temp hum sensors An ambient temperature and humidity sensor has the same appearance as a battery temperature sensor The two types of sensors can be cascaded up to four The ambient temperature and humidity sensor address range is 32 44 which is different...

Page 155: ...ltage are restored to the default values The parameter is configurable after the inverter shuts down If Output voltage level is 380 V or 400 V the default upper threshold is 15 and the default lower threshold is 20 If Output voltage level is 415 V the default upper threshold is 10 and the default lower threshold is 20 The parameter is configurable after the inverter shuts down Item Description Sin...

Page 156: ... voltage threshold are set for cells Advanced Parameters Set System capacity and Power module capacity according to site specifications Incorrect settings may generate an overload alarm which affects normal UPS running Figure 4 35 Advanced Param screen 1 Item Description System capacity kVA The rated system capacity equals the capacity of each power module multiplied by the number of requisite pow...

Page 157: ...ively NOTE Ensure that the BSC signal cable between the master and slave BSC systems is properly connected and that BSC related hardware is properly installed Figure 4 36 Advanced Param screen 2 Item Description Paral sys hibernate If the customer load is light set parallel hibernation to alternate modules in hibernation to prolong their service life as well as improve system efficiency Module cyc...

Page 158: ...efault value is 10 min Inverter async alarm Specifies whether the Inverter async alarm is displayed when the inverter does not track the bypass input The normal power supply is not affected regardless of whether the parameter is Enable or Disable Bus overvoltage recovery Specifies whether to automatically clear the alarm and restart the power module when the rectifier or inverter shuts down due to...

Page 159: ...termines that the inverter capacitor is faulty and shuts down the inverter The default value is 13 A Figure 4 38 Advanced Param screen 4 Item Description Capacitor failure detection lower limit A The value range of Capacitor failure detection lower limit is 0 2 5 A When the inverter capacitor current is lower than the current specified by this parameter the power module determines that the inverte...

Page 160: ...r based on the altitude of the place where the rack is used The default value is less than or equal to 1000 ModbusTCP Encryption If Modbus TCP is used for communication communication links implement encryption based on the selected encryption mode or do not implement encryption Batt charging capacity mismatch This parameter specifies whether the alarm is enabled An alarm is generated only when the...

Page 161: ... control the interval that each rack or module transfers from battery mode to normal mode which reduces the impact on the generator or power grid In the case of battery undervoltage the system automatically shortens the delay for transferring to normal mode to 1 8 of the normal delay to accelerate the transfer and prevent battery overdischarge Intra rack power module start delay s can be set to a ...

Page 162: ...alue range is 0 1 2 0 Hz s and the default value is 0 6 Hz s This parameter can be adjusted based on site requirements If Output freq track rate Hz s is slow the inverter frequency is different from the bypass frequency when the bypass frequency changes If output is overloaded or the inverter is faulty an interruption less than 20 ms occurs when the UPS transfers from normal mode to bypass mode If...

Page 163: ...6 Hz 2 Hz by default Maximum bypass voltage When the difference between the bypass voltage and the rated voltage exceeds the upper threshold for the bypass voltage the system determines that the bypass voltage is not normal and that the bypass is unavailable NOTE When the voltage level is 380 V the value range is 10 15 default 20 and 25 When the voltage level is 400 V the value range is 10 15 defa...

Page 164: ...hnologies Co Ltd 155 Item Description 6 7 8 9 or 10 The default value is 5 BPM mode upon BPM overtemp This parameter specifies whether to start bypass mode if overtemperature occurs Battery Parameter Settings Battery parameter settings impact battery maintenance battery lifespan and UPS discharge time When you set battery parameters note the following ...

Page 165: ...and Single batt dis voltage deviation alarm thres are used to check whether the batteries in each battery string have the same charge voltage and discharge voltage When a value exceeds the specified range an alarm is generated The calculation formula is Charge Discharge voltage Average voltage Average voltage x 100 The charge discharge voltage and average voltage are obtained from the BMU If the B...

Page 166: ...alized charging mode Automatic equalized charging When the value is Enable the UPS automatically changes the battery management status to equalized charging based on the charge current and float charge time Forced equalized charging protection time h Enable forced equalized charging when batteries are continuously under float charging or hibernation When the forced equalized charging time reaches ...

Page 167: ...rotection is not implemented The default value is 24 hours Sched shallow dis test When certain conditions are met the charger shuts down and batteries supply power to loads The system records the battery discharge data as the reference for battery capacity and lifespan Shallow dis test dis ratio Set the proportion of the discharge capacity to the total discharge capacity The value can be 10 50 and...

Page 168: ...ackup time is lower than the warning threshold Remain cap warning An alarm is generated if this parameter is set to Enable and the remaining capacity is lower than the warning threshold Dis cur 0 1C EOD V cell Dis cur 0 3C EOD V cell Dis cur 0 5C EOD V cell and Dis cur 1 0C EOD V cell By default 0 1C EOD V cell is set to 1 80 0 3C EOD V cell to 1 75 0 5C EOD V cell to 1 67 and 1 0C EOD V cell to 1...

Page 169: ...tery string have the same charge voltage and discharge voltage When a value exceeds the specified range an alarm is generated The calculation formula is Charge Discharge voltage Average voltage Average voltage x 100 Dry Contact Settings Set only the dry contacts that are needed Otherwise the UPS may not run properly When a dry contact card is disabled its dry contact signals are disabled After a d...

Page 170: ...nection status Independent input signals can be enabled only when this parameter is set to Enable Batter ground fault BTG Enable or disable the battery grounding failure detection D G connection GEN Enable or disable D G connection detection BCB connection OL Enable or disable BCB connection detection Batter breaker STA Enable or disable battery circuit breaker monitoring PDC output breaker OUT En...

Page 171: ...h BP SYSMT switch function If the BP SYSMT switch is set to Enable this parameter is displayed on the screen Set this parameter to determine whether the port is used to detect the status of the PDU bypass input switch or system maintenance switch SPD SYSOU T Switch If the SPD SYSOUT switch is set to Enable the port has dry contact signal access How a user uses the port depends on the status of the...

Page 172: ...nabled the mains and bypass backfeed protection is enabled MUS05A DO_1 Action Control the status of the DO_1 dry contact on the MUS05A dry contact card MUS05A DO_2 Action Control the status of the DO_2 dry contact on the MUS05A dry contact card MUS05A DO_3 Action Control the status of the DO_3 dry contact on the MUS05A dry contact card MUS05A DO_4 Action Control the status of the DO_4 dry contact ...

Page 173: ...of the DO_3 dry contact on the MUE07 extended dry contact card MUE07A DO_4 Action Control the status of the DO_4 dry contact on the MUE07 extended dry contact card MUE07A DO_5 Action Control the status of the DO_5 dry contact on the MUE07 extended dry contact card Figure 4 52 Dry Contacts screen 5 Item Description MUS05A DO_1 Corresponds to signal of the output dry contact DO_1 on the MUS05A MUS05...

Page 174: ...E07A DO_1 Corresponds to signal of the output dry contact DO_1 on the MUE07A MUE07A DO_2 Corresponds to signal of the output dry contact DO_2 on the MUE07A MUE07A DO_3 Corresponds to signal of the output dry contact DO_3 on the MUE07A MUE07A DO_4 Corresponds to signal of the output dry contact DO_4 on the MUE07A MUE07A DO_5 Corresponds to signal of the output dry contact DO_5 on the MUE07A Figure ...

Page 175: ...ut dry contact DI_3 on the MUE07A MUE07A DI_4 Corresponds to signal of the input dry contact DI_4 on the MUE07A MUE07A DI_5 Corresponds to signal of the input dry contact DI_5 on the MUE07A CIM Parameters If iBAT is configured set the parameters in this section by referring to the document delivered with the iBAT Figure 4 55 shows the CIM Param screen Figure 4 55 CIM parameters On the System Info ...

Page 176: ... A maximum of four CIMs can be connected CIM start address The CIM start address cannot be changed The DIP switch should be set to 0000 for the first CIM and the DIP switch setting for a later connected CIM should increase by 1 binary than that set for the previous CIM CIM Number of BIMs Number of BIMs managed by the CIM Number of battery strings Number of battery strings connected in parallel Bat...

Page 177: ...meters Item Description Current source Specifications of the Hall effect sensor BCB connects to CIM Determine whether the BCB connects to the CIM Batt abnormal BCB trip Determine whether BCB trips when batteries are not functioning properly Multi Hal l cur setting The value of Multi Hall cur setting equals the number of positive or negative Hall effect sensors in a single battery string and should...

Page 178: ...ows the configuration of CIM and BIM for each battery string Figure 4 60 Batt String Config 2 4 1 3 5 Maintenance Screen On the System Info screen tap to display the Maintenance screen as shown in Figure 4 61 and Figure 4 62 The Maintenance screen provides buttons such as Battery Maint USB Operations Inv ON and Inv OFF If a user is not currently logged in a dialog box will display for entering a u...

Page 179: ...i Proprietary and Confidential Copyright Huawei Technologies Co Ltd 170 Figure 4 61 Maintenance screen 1 Figure 4 62 Maintenance screen 2 On the System Info Settings Advanced Param screen when Bus Capa Life is set to Enable the Bus Capa Life is displayed on the Maintenance screen Battery Maint screen ...

Page 180: ...e UPS reliability Battery maintenance includes Forced Equalized Charging Shallow Dis Test and Capacity Test The next maintenance time displayed on the screen indicates the upcoming time in which to check batteries Figure 4 63 shows the Battery Maint screen Figure 4 63 Battery Maint screen Item Description Forced Equalized Charging Forcibly perform equalized charging on batteries Shallow Dis Test T...

Page 181: ...ht Huawei Technologies Co Ltd 172 Figure 4 64 USB Operations screen 1 Figure 4 65 USB Operations screen 2 Inv ON and Inv OFF Menus Use the LCD to start and shut down the inverter Before the inverter starts the system asks for confirmation to prevent misoperations Figure 4 66 shows the Inv ON screen and Figure 4 67 shows the Inv OFF screen ...

Page 182: ...awei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 173 Figure 4 66 Inv ON screen Figure 4 67 Inv OFF screen Item Description Inv ON The Inv ON screen allows you to start the inverter manually Inv OFF The Inv OFF screen allows you to shut down the inverter manually ECM Switchover ...

Page 183: ... an ECM is inserted active and standby switchover is supported only after the ECM is configured and starts working properly about 30 seconds When an ECM needs to be maintained perform active standby switchover on the ECM as shown in Figure 4 68 a dialog box will display asking for confirmation to prevent misoperations After switchover ensure that the ECM has stopped working the yellow or red indic...

Page 184: ...ke the red indicator on the BIM start or stop blinking super fast Internal resistan ce Measure the battery internal resistance If the condition for measuring internal resistance is met batteries are fully charged you can tap Measure to start measuring the internal resistance of the selected BIM in a CIM NOTE The interval between two measurement operations must be greater than 10 minutes Bus Capa L...

Page 185: ...orecast 4 1 3 6 About Screen On the System Info screen tap About to view the UPS model manufacturer name monitoring version and power version as shown in Figure 4 72 To view version details tap Version Info Figure 4 72 About screen 4 1 4 System Status Screen On the main screen tap System Status On the System Status to view the mains input bypass input load and battery information as shown in Figur...

Page 186: ...igure 4 73 System Status screen 4 1 5 Common Functions Screen On the main screen tap Common Functions On the Common Functions to query the AC output load and mains input information start or shut down the inverter start or shut down the inverter control the buzzer and query the historical alarms as shown in Figure 4 74 and Figure 4 75 Figure 4 74 Common Functions screen 1 ...

Page 187: ... Huawei Technologies Co Ltd 178 Figure 4 75 Common Functions screen 2 4 2 WebUI 4 2 1 Login Context Internet Explorer 11 is used as the example browser Procedure Step 1 Open the browser and choose Tools Internet Options Step 2 On the Advanced tab page ensure that Use TLS 1 0 and Use TLS 1 1 are selected and click OK as shown in Figure 4 76 ...

Page 188: ...ble 4 5 describes the system users The preset UPS IP address is 192 168 0 10 You can set the UPS Ethernet IP address on the LCD or WebUI The value range is 1 0 0 0 223 255 255 255 Table 4 5 User description Default User Preset Password User Rights admin system administrator LCD 000001 Performs all operations on the LCD and WebUI including system running information browsing system information hist...

Page 189: ... controls the buzzer Other control and maintenance functions that may affect system operation are invisible and parameters cannot be set WEB Changeme browser browsing user WEB N A Only browses the system running information If an incorrect password is entered three consecutive times the account will be logged out for 5 minutes After a user logs in to the WebUI if another user logs in with the same...

Page 190: ...nvalid or outside the range Table 4 6 Monitoring page details Numb er Area Function 1 Running status area Displays the power flow and UPS running information 2 Menu bar Displays alarms and real time data sets parameters and provides control commands The Active Alarms page is displayed by default 3 Information area Displays system monitoring information 4 2 2 1 Active Alarms Page The Active Alarms ...

Page 191: ...ta Page The Real time Data page details real time system running data as shown in Figure 4 79 Figure 4 79 Real time Data page 4 2 2 3 Param Settings Page Set basic parameters advanced parameters input parameters output parameters bypass parameters battery parameters and dry contacts on the Param Settings page as shown in Figure 4 80 The setting method is the same as that on the LCD For details see...

Page 192: ... 4 80 Param Settings page 4 2 2 4 Comm Config Page Open the Comm Config page to set communications information The settings are the same as those on the LCD in 4 1 3 4 Settings Screen See Figure 4 81 Figure 4 81 Comm Config page 4 2 2 5 CIM Parameters Open the CIM Param Screen to set basic parameters advanced parameters and battery string configurations as shown in Figure 4 82 ...

Page 193: ...ure 4 82 CIM parameters 4 2 2 6 Control Page Open the Control page to control the system running and CIM as shown in Figure 4 83 Figure 4 83 Control page 4 2 3 Query Page 4 2 3 1 Historical Alarms Page On the homepage click the Query tab to open the Historical Alarms page for querying historical alarms based on severity generation time and clear time as shown in Figure 4 84 ...

Page 194: ...ogies Co Ltd 185 Figure 4 84 Historical Alarms page 4 2 3 2 Logs Page On the Logs page you can set Log to Historical logs Cap test logs or Common test logs and query or export logs as shown in Figure 4 85 Historical logs can be exported but not queried Figure 4 85 Logs page 4 2 4 Config Page 4 2 4 1 User Management On the home page choose Config User Mgmt ...

Page 195: ...s and can contain only uppercase and lowercase letters digits and underscores The password contains 6 to 20 characters and at least two types of uppercase letters lowercase letters digits and underscores If the LUI password complexity check is disabled the user password is required to be a string of six to eight digits If the password complexity check is enabled the user password is required to be...

Page 196: ... Trap is incorrectly set or not set system information will be lost or not reported in time The certificate is used for Secure Sockets Layer SSL encryption protection for WebUI login You need to apply to a third party institution for the certificate Configuration Management is used to upload and export configuration parameters in the monitoring system Multi brand Management is used to import the b...

Page 197: ...port a CA certificate to verify the validity of the Modbus TCP access certificate ModbusTCPAuthentication Verify the identity legitimacy of both parties to ensure data security for both parties in ModbusTCP communication After eUPS certificate management is configured a certificate can be imported on the WebUI to replace the preset eUPS certificate 4 2 4 3 RCCMD RCCMD RCCMD function is set to Disa...

Page 198: ...The SSL encrypted transmission set on the page of the UPS5000E monitor display module MDU must be the same as the setting on the RCCMD client SSL Encrypted Transmission is set to Enable by default as shown in Figure 4 90 If it is set to Disable the RCCMD certificate controls will not be displayed on the page as shown in Figure 4 91 If SSL Encrypted Transmission is set to Disable a message indicati...

Page 199: ...nologies Co Ltd 190 Figure 4 90 SSLencrypted transmission enabled by default Figure 4 91 SSLencrypted transmission disabled Event Configuration The MDU supports 17 alarm events and a maximum of 50 jobs can be added for each event as shown in Figure 4 92 Figure 4 92 shows the buttons on the Event Configuration page and Table 4 7 describes these buttons ...

Page 200: ...on 1 Button for expanding all You can view all jobs of all events by clicking this button 2 Button for expanding one event You can view all jobs of the event by clicking this button 3 Button for adding one job You can add one job for the event by clicking this button 4 Button for adding one job for events Select multiple events and you can add one job for the selected events at the same time by cl...

Page 201: ...the job 2 Button for deleting one job You can delete the job by clicking this button 3 Button for test If you click this button the job will be performed and a message showing test succeeds or fails will be displayed on the page Adding one job for one event Select one event for example Inverter on click the button for adding one job and the page for adding a job for the event is displayed When add...

Page 202: ...td 193 RCCMD Shutdown You need to specify the RCCMD client IP address and port When the RCCMD client receives the job it will shut down the computer Figure 4 94 RCCMD shutdown RCCMD Message Specify the RCCMD client IP address port and message to be conveyed The RCCMD client will receive the message For example enter This is a test message Figure 4 95 RCCMD message ...

Page 203: ...the computer after receiving the command Figure 4 96 RCCMD execute RCCMD TRAP When the event happens the MDU will send the TRAP message to all connected RCCMD clients based on the sending mechanism If you want to define the TRAP message by yourself you can use the TRAP signal to display the UPS information For example if you enter INVOLT V the RCCMD client will receive the UPS input voltage value ...

Page 204: ...TPOWER Active power kW OUTVOLT Output voltage V OUTCURR Output current A OUTLOAD Output load rate BATTCAP Remaining battery capacity INVOLT Input voltage V BYPASSINVOLT Bypass input voltage V TEMPDEG Temperature inside the UPS Celsius AUTONOMTIME Battery backup time minutes STATUS UPS status N A RUNTIME UPS operating time minutes BATTVOLT Battery voltage V INFREQ Input frequency Hz BYPASSINFREQ By...

Page 205: ...conds After X seconds on Battery After the battery mode is activated for X seconds the job will be sent to the RCCMD client once At X seconds remaining time When the battery backup time has only X seconds left the job will be sent to the RCCMD client once X and Y are variables and stand for time RCCMD Certificate Management After replacing the certificate on the MDU WebUI replace the certificate o...

Page 206: ...encrypted enable and enter the key password 4 2 4 4 Managing the UPS by Using the NMS Complying with RFC1628 Standard Installing the UPS MIB The MIB is in the MDU Click Download UPS RFC1628 MIB on the page of the web browser to download the MIB file which allows the third party NMS of Generex to manage the UPS remotely Figure 4 99 RCCMD certificate management The UPS RFC1628 MIB has more alarms th...

Page 207: ...ht settings are used for adding information about the NMS accessing the MDU including the NMS address access right and Trap port For details about how to add an NMS over a web browser see Figure 4 100 Figure 4 100 RCCMD certificate management Managing the UPS Take the UNMS of Generex for example The method for managing the UPS by using the UNMS is the same as the method for managing other devices ...

Page 208: ... Manual 50 kVA Power Modules 4 User Interface Issue 02 2017 02 25 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 199 Figure 4 102 Commissioning Var page Figure 4 103 Upgrade page Figure 4 104 Download page ...

Page 209: ...age and Trap message to the RCCMD client if the UPS system generates an alarm executes commands on the RCCMD client Receives the message UPS alive check sent by the RCCMD client and replies with the system status Configures and saves the address and port for receiving the shutdown command and the message sending mechanism For the method of installing the RCCMD client see the manual related to the ...

Page 210: ... the unencrypted mode you need to set the SSL encryption to Disable on the server WebUI Step 4 Configure events If you set the job type to RCCMD Message under Inverter on specify the IP address and port of the RCCMD client The port is 6003 by default If you need to modify the port modify the port on the RCCMD client at the same time to keep them the same Enter the message to be sent and set the me...

Page 211: ...MDU that detects heartbeat needs to be added Then the UPS alive check function is supported the RCCMD can check whether the UPS and RCCMD communicate properly the RCCMD can receive messages sent by the MDU Procedure Step 1 On the RCCMD client add the IP address of the MDU that detects heartbeat as shown in Figure 4 107 Step 2 The UPS5000 MDU supports both ways of heartbeat detection If the job con...

Page 212: ... Modules 4 User Interface Issue 02 2017 02 25 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 203 Figure 4 107 Heartbeat detecting mode on the RCCMD client You can also manually detect heartbeat by clicking Run alive check now ...

Page 213: ...50 kVA Power Modules 4 User Interface Issue 02 2017 02 25 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 204 Figure 4 108 Detecting heartbeat manually Figure 4 109 Detecting heartbeat manually and successfully End ...

Page 214: ...Technologies Co Ltd 205 5 Operations 5 1 Powering On and Starting the UPS Prerequisites Measure the voltage and frequency where the UPS input circuit breakers mains and bypass input circuit breakers on the input PDC or the external input switch is located The voltage range is 138 485 V AC line voltage and the frequency range is 40 70 Hz Context ...

Page 215: ... except for the ready switches for the power module and bypass module which are in locked state Figure 5 1 shows the bypass module ready switch and Figure 5 2 shows the power module ready switch Figure 5 1 Bypass module ready switch Figure 5 2 Power module ready switch Procedure Step 1 Power on the UPS The following describes the details about powering on the UPS in full configuration and in stand...

Page 216: ...itialization progress bar Step 2 After the LCD starts perform the following steps If the UPS is starting for the first time set the language date and time network parameters and system parameters on the Settings Wizard screen If this is not the first startup retain the previous settings After the settings are specified the Bypass mode and No battery alarms are displayed on the LCD The main buttons...

Page 217: ... 3 4 Settings Screen Figure 5 5 Network Param screen After setting network parameters connect the UPS to the network over a network cable which enables remote management of the UPS If remote management is not required retain the default network parameter settings 4 On the System Param screen select Single default value or Parallel as shown in Figure 5 6 Set the Output voltage level Output frequenc...

Page 218: ...g may affect the normal running of the UPS Output voltage level refers to the line voltage level Set it based on the site requirements Set Output frequency correctly otherwise the UPS cannot work properly and the loads may be affected Figure 5 6 System Param 1 screen Battery parameter settings impact the battery maintenance battery lifespan and UPS discharge time Before setting battery parameters ...

Page 219: ...0 Ah 150 Ah If 192 batteries 300 Ah 2 V are connected in series to form a battery string and two of such battery strings connected in parallel and then to the UPS set Number of cells to 192 192 x 1 and Battery capacity to 600 Ah 300 Ah 300 Ah An incorrect setting will cause a high or low charge voltage which greatly shortens the battery lifespan Moreover the UPS may shut down before the batteries ...

Page 220: ...ked out for 5 minutes b On the LCD choose Common Functions and tap Inv ON c In the displayed dialog box tap Yes to start the inverter as shown in Figure 5 9 Figure 5 9 Starting the inverter You can also choose System Info Maintenance In the Maintenance screen start the inverter Over the WebUI a Open the browser Internet Explorer 11 as an example and choose Tools Internet Options The UPS supports I...

Page 221: ...and Confidential Copyright Huawei Technologies Co Ltd 212 Figure 5 10 Settings in the Internet Options dialog box c Enter https UPS IP address in the address box of the browser d Select a language Enter a User name and Password and click Login to open the homepage as shown in Figure 5 11 Figure 5 11 WebUI login ...

Page 222: ...nd when it cannot be started the startup command will be kept for 1 minute If the startup command is not cleared within 1 minute for example other faults occur on the module or shutdown or fault rectification is performed and the module can be started the module responds to the startup command Step 6 After the inverter starts the UPS works in normal mode The Bypass mode alarm disappears Check that...

Page 223: ...ensure that the battery strings are connected properly Number of cells indicates the number of 2 V cells connected to the UPS Number of cells affects the charge voltage and discharge time An incorrect setting will cause a high or low charge voltage which greatly shortens the battery lifespan Moreover the UPS may shut down before the discharging is completed which may result in data backup failure ...

Page 224: ... are multiple battery strings close the switch for each battery string and then close the general switch between the battery strings and the UPS After the battery switch is closed the No battery alarm disappears on the MDU Step 9 Optional If the BCB box is configured choose Settings Dry Contacts set MUE05A connection to Enable and then set BCB connection OL and Battery breaker STA to Enable Figure...

Page 225: ...Shut down the inverter On the LCD a On the main screen tap Common Functions Tap Inv OFF b If no user is not logged in enter a user name and password and tap on the login screen displayed Table 4 5 lists the default user names and preset passwords and describes the permission of the default users If an incorrect password is entered three consecutive times the account will be logged out for 5 minute...

Page 226: ...he homepage choose Monitoring Control and click Inv OFF In the displayed dialog box click OK to shut down the inverter Figure 5 17 Shutting down the inverter After the inverter shuts down the UPS works in bypass mode if the bypass is normal as shown in Figure 5 18 the UPS supplies no power and the loads power off if the bypass is abnormal as shown in Figure 5 19 Figure 5 18 Normal bypass After you...

Page 227: ... and output switch 2 Open the external mains and bypass input switches Step 5 For a UPS in standard configuration open the external mains and bypass input switches End 5 3 Starting the UPS in Battery Mode Procedure Step 1 Ensure that batteries are properly connected Use a multimeter to check that the sum of the absolute voltages of positive and negative battery strings are greater than a certain v...

Page 228: ... following Step 4 and Step 5 in section 5 1 Powering On and Starting the UPS End 5 4 Transferring to Bypass Mode Before shutting down the inverter ensure that the bypass is normal If the bypass is not normal after the inverter is shut down the UPS supplies no power and the loads shut down Perform Step 1 in section 5 2 Shutting Down and Powering Off the UPS to shut down the inverter over the LCD or...

Page 229: ...upport the ECO mode for higher efficiency To avoid frequent transfer between ECO mode and normal mode do not set the ECO mode when the bypass input is unstable or is sensitive to load changes ECO mode is not recommended when the load is less than 10 Before transferring the UPS to ECO mode ensure that the bypass module works properly Procedure Step 1 Manually shut down the inverter to transfer the ...

Page 230: ...2 Setting ECO mode Step 4 Manually start the inverter After the inverter starts the UPS still works in bypass mode and the inverter is on standby Figure 5 23 shows the power flow displayed on the System Status screen If the bypass is not normal the inverter supplies power immediately If the inverter is not started the UPS may be disconnected Figure 5 23 System Status screen End ...

Page 231: ...rocedure Step 1 On the main screen of the LCD tap System Info Tap The Maintenance screen is displayed Step 2 Optional If no user is logged in enter a user name and a password and then tap For details about default user names preset passwords and user rights see Table 4 5 If an incorrect password is entered three consecutive times the account will be logged out for 5 minutes Step 3 On the Maintenan...

Page 232: ...r overcurrent alarm An alarm is generated End 5 6 2 Shallow Discharge Test Context Before a shallow discharge test ensure that The UPS works in normal mode with a load ratio fluctuation less than 10 The UPS has generated no battery overtemperature overvoltage or overcurrent alarm No generator is connected to the UPS The mains batteries charger and discharger are normal No overload alarm is generat...

Page 233: ...w Dis Test to start a shallow discharge test as shown in Figure 5 26 Figure 5 26 Starting a shallow discharge test When the battery test is complete the test data is used as common test data Record the data obtained from the latest five tests Tap Stop next to Shallow Dis Test in any of the following cases The battery discharge capacity reaches the specified value 10 50 20 by default The discharge ...

Page 234: ...rd and then tap For details about default user names preset passwords and user rights see Table 4 5 If an incorrect password is entered three consecutive times the account will be logged out for 5 minutes Step 3 On the Maintenance screen tap Battery Maint as shown in Figure 5 24 Step 4 Tap Start next to Capacity Test to start a capacity test as shown in Figure 5 27 Figure 5 27 Starting a capacity ...

Page 235: ...stem Info Tap The Maintenance screen is displayed Step 3 Optional If no user is logged in enter a user name and a password and then tap For details about default user names preset passwords and user rights see Table 4 5 If an incorrect password is entered three consecutive times the account will be logged out for 5 minutes Step 4 Choose USB Operations Export Logs and select a log download path as ...

Page 236: ...ies Co Ltd 227 Figure 5 29 Confirming the path End 5 6 4 2 Download over the WebUI Procedure Step 1 Log in to the WebUI Step 2 Choose Query Logs select Cap test logs or Common test logs from the Log drop down list box then click Export to export logs as shown in Figure 5 30 and Figure 5 31 Figure 5 30 Capacity test logs Figure 5 31 Common test logs End ...

Page 237: ... 1 Transfer the UPS to the bypass mode by referring to Step 1 in 5 2 Shutting Down and Powering Off the UPS Step 2 Close the maintenance bypass switch by performing the following actions according to the UPS version being used For the UPS5000 E 200K SM rotate the handle clockwise 90 degrees so that the handle points downwards as shown in Figure 5 32 For the UPS5000 E 200K FM remove the barrier chi...

Page 238: ...odules 5 Operations Issue 02 2017 02 25 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 229 Figure 5 32 Closing the maintenance bypass switch UPS5000 E 200K SM Figure 5 33 Closing the maintenance bypass switch UPS5000 E 200K FM ...

Page 239: ...odules 5 Operations Issue 02 2017 02 25 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 230 Figure 5 34 Closing the maintenance bypass switch UPS5000 E 300K SM Figure 5 35 Closing the maintenance bypass switch UPS5000 E 300K SMT ...

Page 240: ...to normal mode ensure that the bypass input and output are normal Procedure Step 1 Open the maintenance bypass switch by performing the following actions according to the UPS version being used For the UPS5000 E 200K SM rotate the handle counterclockwise 90 degrees so that it points rightwards as shown in Figure 5 37 For the UPS5000 E 200K FM pull down the switch as shown in Figure 5 38 For the UP...

Page 241: ...pening the maintenance bypass switch UPS5000 E 200K SM Operations on the UPS5000 E 200K SM and UPS5000 E 300K SM SMT are similar The operation of the maintenance switch on the UPS5000 E 200K SM is used as an example Figure 5 38 Opening the maintenance bypass switch UPS5000 E 200K FM Step 2 Start UPS inverters For details see Step 4 to Step 5 in 5 1 Powering On and Starting the UPS ...

Page 242: ...EPO After the EPO button is turned on the UPS supplies no power and the loads shut down In maintenance bypass mode the UPS continues to supply power even after the EPO button is turned on Press the EPO button connected to the dry contact card on the UPS or remove the 4 pin terminal from the EPO port on the dry contact card Figure 5 39 EPO ports Figure 5 40 EPO alarm displayed on the LCD ...

Page 243: ...u press the EPO button the EPO and No power supplied alarms are displayed on the LCD 5 10 Clearing the EPO State Procedure Step 1 Clear the EPO state Ensure that the EPO button connected to the dry contact card is not in the EPO state Step 2 Clear the EPO alarm On the LCD On the LCD choose System Info Alarms and tap Clear Faults If you have not logged in a login screen is displayed Enter a user na...

Page 244: ... 42 Alarms In the displayed dialog box tap Yes The EPO alarm is cleared successfully Figure 5 43 Clearing faults On the WebUI In a web browser enter the UPS IP address and select a display language Enter a user name and password and click Login to open the homepage Choose Monitoring Control System Commands and Tests and click Clear Fault The EPO alarm is cleared successfully ...

Page 245: ... normal the UPS transfers to bypass mode Viewing active alarms on the LCD Choose System Info Alarms and tap Active Alarms to check that the EPO alarm is cleared Figure 5 45 Active alarms Viewing active alarms on the WebUI In a web browser enter the UPS IP address and select a display language Enter a user name and password and click Login to open the homepage Choose Monitoring Active Alarms to che...

Page 246: ...ep 4 Start the inverter For details see the section Powering On and Starting the UPS End 5 11 Exporting Data Prerequisites You have logged in to the WebUI Context The following data can be exported Historical alarms Logs E Label CIM version Serviceable data This topic describes how to export historical alarms Procedure Step 1 Choose Query Historical Alarms and set Severity Generated and Cleared ...

Page 247: ...ep 2 Click Query and you can see the corresponding historical alarms Figure 5 48 Exporting historical alarms Step 3 Click Export and save the displayed webpage End 5 12 Setting Hibernation Mode When the load power is small and stable the inverters in some power modules shut down so that these power modules enter hibernation state and the other power modules bear all the load power This improves th...

Page 248: ...repeatedly Before you start hibernation mode check that the number of redundant power modules and racks are appropriate If the number is insufficient the UPS may not enter hibernation mode You can set hibernation mode on the LCD or WebUI 5 12 1 LCD Procedure Step 1 On the main screen tap System Info and The Settings screen is displayed If you have not logged in enter a user name and password and t...

Page 249: ... Yes A message is displayed indicating that the hibernation function is set successfully Step 5 Set Module cycle hiber period d to an integer ranging from 1 to 100 The default value is 30 End 5 12 2 WebUI Procedure Step 1 On the login page enter a user name and password and click Login Step 2 Choose Monitoring Param Settings Advanced Param as shown in Figure 5 51 Figure 5 51 Hibernation parameters...

Page 250: ... Proprietary and Confidential Copyright Huawei Technologies Co Ltd 241 Step 3 On the WebUI set Paral sys hibernate to Enable and click Submit Click Submit after you set the parameter on the WebUI Step 4 Set Module cycle hiber period d to an integer ranging from 1 to 100 The default value is 30 End ...

Page 251: ... If the components are to be maintained contact Huawei technical support Only maintenance engineers can maintain power modules and bypass modules Maintain UPSs regularly based on the following requirements Otherwise the UPSs may fail to operate properly and the service life may be shortened 6 1 1 Monthly Maintenance Table 6 1 Monthly maintenance Check Item Expected Result Troubleshooting Operating...

Page 252: ... Result Troubleshooting Cleanliness Wipe the cabinet surface using a white paper and the paper does not turn black Remove the dust especially from the air filter on the front door or replace the air filter Parameter configuration The configuration of the output voltage grade frequency number of batteries and battery capacity meets requirements Reset the parameters Status record Record the three ph...

Page 253: ... of some key UPS components you are advised to check the key components on a regular basis and replace them within the service life Table 6 4 lists the service life parameters for key components and recommended replacement intervals Table 6 4 Service life parameters for replaceable components and recommended replacement intervals Key Component Design Service Life Recommended Replacement Interval P...

Page 254: ...ife Only professionals are allowed to perform the maintenance tasks 6 2 2 Monthly Maintenance Table 6 5 Monthly maintenance Item Expected Result Troubleshooting Battery management alarm No battery management alarm is generated Identify the cause of an alarm based on the alarm information Battery appearance 1 The surface is clean and tidy without stains 2 The battery terminals are intact 3 Batterie...

Page 255: ...ature displayed on the MDU is less than 3 C 1 Install the temperature sensor in the correct position 2 Replace the battery temperature sensor Battery management parameter settings The settings of battery management parameters meet the requirements in the user manual Set parameters correctly Tightness of battery screws The location of the signs marked on battery terminals indicating tight connectio...

Page 256: ...ed Result Troubleshooting Capacity Test When the UPS is backed up discharge a battery to the undervoltage alarm threshold to refresh the capacity of the battery 1 Locate the cause when an exception is identified 2 If the fault persists contact Huawei technical support Battery connection reliability 1 Each battery terminal is connected reliably When battery strings are powered off check the reliabi...

Page 257: ...st To restore battery discharge after batteries reach EOD use one of the following methods 1 Switch to another battery string Ensure that each battery has a voltage greater than the EOD voltage and 11 3 V cell 2 Restore the mains power supply to start the inverter Close the battery switch and charge batteries until each battery has a voltage greater than the EOD voltage and 11 3 V cell For details...

Page 258: ...ing function fails The charger fails Replace the power module The charger experiences overcurrent Replace the power module The charger experiences undervoltage Check whether the configured number of batteries is correct If the value is correct but the alarm persists replace the power module The UPS works in bypass mode and does not transfer to inverter mode When the mains is normal the UPS works i...

Page 259: ... requires the configuration of IP21 components IP20 Dimensions H x W x D 2000 mm x 600 mm x 850 mm Communicat ion Dry contacts RS485 and SNMP Weight The product weighs 320 kg Each power module is 32 kg A maximum of four power modules are supported The product weighs 410 kg Each power module is 32 kg A maximum of six power modules are supported The product weighs 350 kg Each power module is 32 kg A...

Page 260: ...1000 V AC 630 A 3P N A N A N A UPS5000 E 30 0K SMT 1000 V AC 630 A 3P N A N A N A 8 3 Environmental Specifications Item UPS5000 E 200K SM FM UPS5000 E 300K SM SM T Operating temperature 0 40 C Storage temperature 40 C to 70 C Humidity 0 95 RH non condensing Altitude 0 1000 m When the altitude is greater than 1000 m but less than 4000 m the rated power should be derated For details see the IEC62040...

Page 261: ...C The UPS works at full load when the voltage is 187 280 V AC and is derated to 40 load when the voltage is 187 80 V AC At 30 C The UPS works at full load when the voltage is 176 280 V AC and is derated to 40 load when the voltage is 176 80 V AC Rated frequency 50 Hz 60 Hz Input frequency 40 70 Hz Input PF 0 99 full load 0 98 half load THDi 3 full linear load 5 full non linear load 8 6 Bypass Inpu...

Page 262: ...is derated to 0 8 Battery management Intelligent battery management Cold start In the case of a mains failure batteries can start the UPS to power loads Battery string sharing Battery string sharing is supported in a parallel system No battery string is shared by default Charge voltage Equalized voltage 2 3 2 4 V Cell default 2 35 V Cell 30 42 batteries Equalized voltage 2 3 2 35 V Cell default 2 ...

Page 263: ...e 3 phase unbalance 2 Overload capability Inverter overload capability 105 load 110 transfer to bypass mode after 60 min 110 load 125 transfer to bypass mode after 10 min 125 load 150 transfer to bypass mode after 1 min Bypass overload capability Temperature 30 C load 135 run for a long time Temperature 40 C load 125 run for a long time 1000 load run for 100 ms 8 9 System Electrical Specifications...

Page 264: ...ary and Confidential Copyright Huawei Technologies Co Ltd 255 A Optional TN C System Application Figure A 1 to Figure A 4 show cable connections for short circuiting the input N and PE for different UPS models The following cable connections are for reference only Figure A 1 Short circuiting the input N and PE UPS5000 E 200K SM ...

Page 265: ... Optional TN C System Application Issue 02 2017 02 25 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 256 Figure A 2 Short circuiting the input N and PE UPS5000 E 200K FM Figure A 3 Short circuiting the input N and PE UPS5000 E 300K SM ...

Page 266: ...tial Copyright Huawei Technologies Co Ltd 257 Figure A 4 Short circuiting the input N and PE UPS5000 E 300K SMT Table A 1 lists the recommended cross sectional areas for cables Table A 1 Recommended cross sectional areas for cables Model Current A Recommended Cross Sectional Area mm2 UPS5000 E 200K SM FM 335 4 95 UPS5000 E 300K SM SMT 533 1 150 ...

Page 267: ... Menu Level 2 Menu Level 3 Menu Level 4 Menu System Info Runn Info AC Output N A UPS Load N A Mains Input N A Bypass Input N A Battery Status N A Module Data N A Total Runtime N A Environment Data N A Alarms Active Alarms N A Historical Alarms N A Buzzer Off N A Clear Faults N A Settings Basic N A Communication N A Basic Param N A Advanced Param N A Input Param N A Output Param N A Bypass Param N ...

Page 268: ... Param Advanced Param Maintenance Battery Maint N A USB Operations Remove USB Upgrade Software Load Config Export Config Export Logs Export E labels Export Alarms Multi brand Serviceable data CIM Version Inv ON N A Inv OFF N A ECM Switchover N A Screen Calib N A CIM Maint N A About Model N A Manufacturer N A Monitoring Version N A Power Version N A Version Info N A Common Functions AC Output Phase...

Page 269: ... A Load ratio N A Crest factor N A Mains Input Phase voltage N A Line voltage N A Phase current N A Frequency N A Power factor N A Inv ON N A N A Inv OFF N A N A Buzzer Off N A N A Historical Alarms N A N A System Status Bypass N A N A Mains N A N A Load N A N A Battery N A N A B 2 Menus on the WebUI Level 1 Menu Level 2 Menu Level 3 Menu Level 4 Menu Level 5 Menu Monitorin g Active Alarms N A N A...

Page 270: ...enu Level 5 Menu Bypass Phase voltage Line voltage Current Power factor Frequency Output Phase voltage Line voltage Current Power factor Frequency Crest factor Load ratio Active power Apparent power Reactive power System active power System apparent power System reactive power Battery Voltage Current Bus voltage Battery temperature Backup time Remaining capacity SOH Environment Data Ambient temper...

Page 271: ...tage Current Power factor Frequency Zero sequence current Bus voltage Battery voltage Battery current Inverter Phase voltage Line voltage Current Inductance current Output phase voltage Frequency Active power Apparent power Reactive power Power factor Load ratio Crest factor Battery String N A N A Param Settings Basic Param Single Parallel N A Voltage level N A Output frequency N A Battery capacit...

Page 272: ...N A Paral sys hibernate N A Module cycle hiber period N A High ambient temperature alarm threshold N A Low ambient temperature alarm threshold N A Top outlet fan N A EOD restart N A EOD restart delay N A Inverter async alarm N A Bus overvoltage recovery N A Bus overvolt recovery time N A Capacitor failure detection N A Capacitor failure detection upper limit N A Capacitor failure detection lower l...

Page 273: ... N A Battery segment detection N A Emergency Shut Down Enable N A Input Param D G mode N A D G power limiting N A D G charger power ratio N A Intra rack power module start delay N A Inter rack power module start delay N A Input adaptability N A Output Param Output volt adjustment N A Outp transf interrupt time N A Self load output cur ratio N A Output interruption transfer time N A Max BPM transfe...

Page 274: ...hg cur limiting coef N A Cell float voltage N A Cell equalized volt N A Transfer to equalize d charging cur coef N A SOC to start equalized charging N A Automatic equalized charging N A Forced equalized charging protection time N A Equalized charging protection interval N A Scheduled equalized charging interval N A Float volt temp comp N A Float volt temp comp coef N A Max batt dis time N A Sched ...

Page 275: ... thresh N A Remain cap warning N A Remain cap warn thresh N A Dis cur 0 1C EOD N A Dis cur 0 3C EOD N A Dis cur 0 5C EOD N A Dis cur 1 0C EOD N A Intelligent hibernation N A Class 1 grid hiber time N A Class 2 grid hiber time N A Single batt float chg voltage deviation alarm thres N A Single batt dis voltage deviation alarm thres N A Dry Contacts MUE05A connection N A Battery ground fault N A D G ...

Page 276: ...A BP SYSMT switch function N A SPD SYSOUT Switch N A SPD SYSOUT switch function N A MUE06A connection N A MUS05A DO_1 Action N A MUS05A DO_2 Action N A MUS05A DO_3 Action N A MUS05A DO_4 Action N A MUE07A DO_1 Action N A MUE07A DO_2 Action N A MUE07A DO_3 Action N A MUE07A DO_4 Action N A MUE07A DO_5 Action N A MUS05A DO_1 N A MUS05A DO_2 N A MUS05A DO_3 N A MUS05A DO_4 N A MUE07A DO_1 N A MUE07A ...

Page 277: ...net mask N A Gateway N A NAT mapping N A Serial Port Settings RS485 Com Baud Rate N A RS485 Com Address N A Parity mode N A Stop bit N A Battery Temperature Sensor Settings Start addr of batt temp sensor N A Batt temp sensors N A Ambient Temperature and Humidity Sensor Settings Start address of ambient temperature and humidity sensors N A Ambient temperature and humidity sensors N A BMU Settings B...

Page 278: ...ource N A BCB connects to CIM N A Batt abnormal BCB trip N A Multi Hall cur setting N A Batt String Config N A N A Control System Commands and Tests Inv ON N A Inv OFF N A Clear Fault N A Bypass runtime Clear N A Inv runtime Clear N A Forced equalized charging Start Stop N A Shallow discharge test Start Stop N A Capacity Test Start Stop N A CIM Control CIM No N A BIM No N A Reset CIM BIM N A Blink...

Page 279: ... A Delete N A Lock N A Unlock N A LUI password complexity check N A Idle Timeout Logout Allowed timeout N A Site Config Time zone Time zone N A System Date and Time Date Local N A Time Local N A System Information Name N A Location N A Contact information N A SNMP SNMP version N A SNMP port N A SNMP Trap No N A Trap addr N A Trap port N A SNMP version N A User name Community N A Certificate Manage...

Page 280: ...ort N A Secure connection TLS encryption N A User account authentication required when sending a mail N A Configure Alarm Notification Email Address No N A Email N A Language N A Alarm Severity N A Scheduled Notifi N A ModbusTCP Certificate Management Upload N A Password N A Confirm password N A ModbusTCP CA Certificate Management Upload N A ModbusTCP Authentication Authentication N A New password...

Page 281: ...t the RCCMD certificate key to be uploaded N A Select the RCCMD CA certificate to be uploaded N A Maint Calib Bypass Ph A input volt N A BPM ph B input volt N A BPM ph C input volt N A Ph A output volt N A Ph B output volt N A Ph C output volt N A Module Ph A input volt N A Ph B input volt N A Ph C input volt N A Ph A input cur N A Ph B input cur N A Ph C input cur N A Pos bus volt N A Neg bus vol...

Page 282: ...cur N A Inv ph A volt N A Inv ph B volt N A Inv ph C volt N A Ph A output volt N A Ph B output volt N A Ph C output volt N A Inv ph A cur N A Inv ph B cur N A Inv ph C cur N A Inv ph A induc cur N A Inv ph B induc cur N A Inv ph C induc cur N A ECM BPM ph A input volt N A BPM ph B input volt N A BPM ph C input volt N A Rack ph A output cur N A Rack ph B output cur N A Rack ph C output cur N A Rack...

Page 283: ...r 0 data N A BPM SW commissioning var 1 data N A BPM SW commissioning var 2 data N A BPM SW commissioning var 3 data N A BPM SW commissioning var 4 data N A BPM SW commissioning var 5 data N A Module Rec SW commissioning var 0 data N A Rec SW commissioning var 1 data N A Rec SW commissioning var 2 data N A Rec SW commissioning var 3 data N A Rec SW commissioning var 4 data N A Rec SW commissioning...

Page 284: ...ioning var 2 data N A Inv SW commissioning var 3 data N A Inv SW commissioning var 4 data N A Inv SW commissioning var 5 data N A ECM ECM SW commissioning var 0 data N A ECM SW commissioning var 1 data N A ECM SW commissioning var 2 data N A ECM SW commissioning var 3 data N A ECM SW commissioning var 4 data N A ECM SW commissioning var 5 data N A Upgrade Upgrade UPS Software N A N A Download Down...

Page 285: ...e mains input is not normal if the mains voltage is less than 272 V the sampling circuit of the power module is not normal Replace the faulty module 0001 2 Cable connectio ns are incorrect The mains is not normal The mains input fuse for the power module is blown 1 Check whether cables to mains are disconnected loose or incorrectly connected 2 If cable connections are correct measure the mains vol...

Page 286: ...excluding 80 V to 176 V If no the mains monitoring circuit for the power module is faulty Replace the faulty module 0010 1 Abnormal bypass voltage Minor The bypass voltage range is not correctly set The bypass input voltage is not normal 1 Check the bypass input voltage or cable connections with a multimeter 2 Check the voltage system and bypass voltage thresholds configured on the LCD 0010 2 The ...

Page 287: ...ng a multimeter If no correct the installation 2 Check whether the battery input voltage of the UPS is normal If yes the battery sampling circuit of the power module is faulty Replace the power module 0021 1 Battery EOD Critical The battery voltage reaches the EOD voltage threshold due to continuous discharge If the BCB box is configured check whether the BCB box trips If it trips close the BCB bo...

Page 288: ...f this alarm is generated in normal mode check whether the battery switch is ON If yes the charger may be faulty Replace the related power module 0530 1 Battery ground fault Critical The battery string is not properly grounded The battery ground monitorin g cable is faulty The dry contact board is faulty 1 Check whether the positive and negative terminals of the battery string are grounded or have...

Page 289: ...attery maintenanc e reminder Warning The time for maintenance arrives Maintain the batteries 0037 1 Battery undervoltag e Critical The UPS has worked in battery mode for an extended amount of time The charger is faulty 1 Check whether the battery voltage is normal 2 Check whether the output is overloaded 3 Check whether any battery is damaged If yes replace the battery 4 Check whether any battery ...

Page 290: ...module 0043 2 The fan is faulty Check the fan or replace the bypass module 0043 3 The fan is faulty The fan monitorin g cable is faulty 1 Replace the fan 2 Check the fan monitoring cable 0043 4 0047 1 Not ready Critical The ready switch is OFF Close the ready switch 0060 4 Inverter abnormal Critical A load short circ uit occurs A short circuit occurs inside the module This fault seldom occurs 1 Ch...

Page 291: ...fter the inverter relay is closed close the bypass input circuit breaker 10 seconds later 0564 1 Overload timeout Critical The load is excessive Derating reduces the rated system power The module is damaged 1 Check that there is no overload 2 Check that the module power is not derated due to a fan fault 3 If the alarm persists replace the power module 0565 1 Load impact transfer to bypass Minor A ...

Page 292: ...ly or the air channel is blocked The ambient temperatu re exceeds the upper threshold The load is excessive 1 Check the bypass fan and air channel If the fan is faulty replace it 2 Check that the ambient temperature has not exceeded 40 C 3 Check that there is no overload 0583 1 Inter rack par cable abnormal Critical The inter rack parallel system CAN bus is disconnec ted or short circ uited Only o...

Page 293: ...broken The parallel CAN bus is broken 0584 2 Inter rack par cable alarm Minor The inter rack parallel cable is faulty Replace the inter rack parallel cable 0584 4 The inter rack industrial frequency synchronizati on cable is broken 0085 1 EPO Critical The EPO button is pressed Restore the EPO button status Start the UPS after the alarm is cleared 0086 1 Max number of BPM transfers Minor The system...

Page 294: ... overloaded Check that the configured rack capacity meets requirements 0090 1 Dry contact board fault Critical I2C communicati on with the dry contact board MUE05A fails Replace the dry contact board MUE05A 0090 2 I2C communicati on with the dry contact board MUE06A fails Replace the dry contact board MUE06A 0356 Battery Mode Minor The UPS is working in battery mode The running status is displayed...

Page 295: ...e alarm persists tap the Clear Fault button to clear the alarm 0341 PDC Maint breaker closed Minor The maintenance circuit breaker on the PDC is ON The running status is displayed No further measures are required 0342 Mains input breaker open Critical The mains input circuit breaker is OFF The running status is displayed No further measures are required 0343 BPM input breaker open Critical The byp...

Page 296: ...CO bypass voltage or frequency is out of the preset range The ECO bypass voltage or frequency range is incorrectl y set The bypass input sequence is reverse or the neutral wire is disconnec ted 1 Check the bypass input voltage and frequency 2 Check that the rated voltage rated frequency ECO bypass voltage range and frequency range are correctly set 3 Check that the bypass cables and circuit breake...

Page 297: ...y track rate is incorrectl y set 1 Check that the bypass output frequency does not change fast 2 Check that the Output freq track rate is properly set 0101 1 BSC signal abnormal Minor The dual bus connector is loose Parameter s are set incorrectl y 1 Check the dual bus connector 2 Check the parameter settings 0102 1 Maint breaker misoperatio n Critical The user operation is incorrect 1 Shut down t...

Page 298: ...d Abbreviations A ASIC application specific integrated circuit ATS AC transfer switch AWG American wire gauge B BSC bus synchronization controller BCB BOX battery circuit breaker box BBB BOX battery bus bar box C CAN control area network CE Conformite Europeenne D DSP digital signal processing E ECO economy control operation EPO emergency power off ECM energy control module EOD end of discharge F ...

Page 299: ...CD liquid crystal display M MDU monitor display unit N NC normally closed NO normally open NTC negative temperature coefficient P PDC power distribution cabinet PE protective earthing PDU power distribution unit R RS485 Recommend Standard 485 S SNMP Simple Network Management Protocol SOC state of charge SOH state of health STS static transfer switch T THDi total distortion of the input current wav...

Page 300: ...VA Power Modules D Acronyms and Abbreviations Issue 02 2017 02 25 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 291 U UPS uninterruptible power system USB Universal Serial Bus V VRLA valve regulated lead acid battery ...

Reviews: