UPS2000-G-(1 kVA-3 kVA)
User Manual (2016, Russia)
9 Specifications
Issue 02 (2016-07-28)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
54
Specifications
1 kVA
2 kVA
3 kVA
Output
Output voltage
200 V AC, 208 V AC, 220 V AC, 230 V AC, 240 V AC
Mains voltage range
±1% (battery mode)
Frequency range
(synchronization range)
47–53 Hz or 57–63 Hz
Frequency range (battery
mode)
50 Hz (tolerance ±0.25 Hz) or 60 Hz (tolerance ±0.3 Hz)
Inverter overload
capability
When the ambient temperature is 0–35°C:
−
105%–110%: The UPS automatically shuts down (in
battery mode) or transfers to bypass mode (in line
mode) after 10 minutes.
−
110%–130%: The UPS automatically shuts down (in
battery mode) or transfers to bypass mode (in line
mode) after 1 minutes.
−
130%–150%: The UPS automatically shuts down (in
battery mode) or transfers to bypass mode (in line
mode) after 3 seconds.
−
> 150%: The UPS automatically shuts down (in battery
mode) or transfers to bypass mode (in line mode) after
0.5 seconds max.
When the ambient temperature is 35–40°C:
−
105%–110%: The UPS automatically shuts down (in
battery mode) or transfers to bypass mode (in line
mode) after 5 minutes.
−
110%–130%: The UPS automatically shuts down (in
battery mode) or transfers to bypass mode (in line
mode) after 30 seconds.
−
130%–150%: The UPS automatically shuts down (in
battery mode) or transfers to bypass mode (in line
mode) after 1.5 seconds.
−
> 150%: The UPS automatically shuts down (in battery
mode) or transfers to bypass mode (in line mode) after
0.5 seconds max.
Bypass overload capability
110%–120%, 30 minutes
120%–130%, 10 minutes
130%–150%, 1 minute
Harmonic distortion
≤ 3% THDv (linear load)
≤ 6% THDv (non-linear load)
Transfer time Transferri
ng from
normal
mode to
battery
0