UPS2000-G-(1 kVA-3 kVA)
User Manual (2016, Russia)
5 Operations
Issue 02 (2016-07-28)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
41
2.
Set the voltage level based on the actual output voltage. The voltage level can be set to
200 V, 208 V, 220 V, 230 V (default), or 240 V.
Figure 5-2
Setting the output voltage
3.
Set the system output frequency based on the rated frequency. The values include 50 Hz,
60 Hz, and AUT (default).
Figure 5-3
Setting the system output frequency
4.
Set the battery capacity to the total capacity of all batteries actually connected. The
default value is 9 Ah for the UPS, and the value can range from 9 Ah to 999 Ah.
Figure 5-4
Setting the battery capacity
5.
Start the UPS to inverter mode.
Hold down the
ON/MUTE
button on the front panel for over 5 seconds to make the UPS
transfer to inverter mode output. The default value is 230 V.