UPS2000-G-(1 kVA-3 kVA)
User Manual (2016, Russia)
4 Setting Control Panel
Issue 02 (2016-07-28)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
22
Figure 4-3
Setting parameters on the LCD
When the UPS is in standby mode or bypass mode, hold down
SELECT
for 5 seconds to start
setting UPS parameters.
When the UPS is in normal mode or battery mode, hold down
SELECT
for 5 seconds to start
setting only for 11 UPS buzzer parameters.
During the setting of UPS parameters, press
ON/MUTE
for more than 3 seconds. Release the
button when you hear a beep sound to select the previous option. During the setting of UPS
parameters, press
SELECT
for more than 3 seconds. Release the button when you hear a
beep sound to select the next option. Press
OFF/ENTER
for more than 3 seconds to confirm
the setting.
The following figures show the twelve parameter setting screens.
01: Set the output voltage.
Display
Setting
The output voltage can be set as follows:
200:
The output voltage is 200 V AC.
208:
The output voltage is 208 V AC.
220:
The output voltage is 220 V AC.
230:
The output voltage is 230 V AC
(default value).
240:
The output voltage is 240 V AC.
02: Enable or disable the frequency conversion mode.