UPS2000-G-(1 kVA-3 kVA)
User Manual (2016, Russia)
7 Routine Maintenance
Issue 02 (2016-07-28)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
47
Keep the battery switch off when installing or maintaining the batteries.
Precautions
Before battery maintenance, get the tools, such as handles, insulated. Do not place metal
tools on exposed battery terminals.
Never use any organic solvent to clean batteries.
Never try to remove the safety valve or fill anything into batteries.
Never smoke or use fire around batteries.
After battery discharge, charge batteries to ensure a required battery capacity.
Only professionals are allowed to perform maintenance tasks.
Routine maintenance items for batteries
Table 7-2
Routine maintenance items for batteries
Item
Expected Result
Measures
Maintenance
Interval
Battery alarm
No battery alarm is
generated.
Identify the cause
based on the alarm
information.
Monthly
Battery appearance
1.
The surface is
clean and tidy
without stains.
2.
The battery
terminals are
intact.
3.
Batteries are free
from damage and
cracks.
4.
Batteries are free
from acid
leakage.
5.
Batteries are not
deformed or
bulged.
If the battery
appearance is
abnormal, contact
Huawei technical
support.
Monthly
Battery operating
temperature
1.
The ambient
battery
temperature is
25±5°C.
2.
The battery
operating
temperature is
lower than
battery
tempe
20°C.
3.
Battery charge
and discharge
conditions meet
1.
Identify the
cause of the
abnormal battery
operating
temperature.
2.
If the fault
persists, contact
Huawei technical
support.
Monthly