UPS2000-G-(1 kVA-3 kVA)
User Manual (2016, Russia)
4 Setting Control Panel
Issue 02 (2016-07-28)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
20
Figure 4-2
Schematic Buttons
Table 4-4
Button description
Button
Function
ON/MUTE
Starting the UPS: Hold down
ON/MUTE
for over 5
seconds to connect the UPS power supply.
Enabling or disabling the buzzer: Hold down
ON/MUTE
for 2–5 seconds to enable or disable the buzzer. However,
when the UPS sends a new alarm, the mute function is
unavailable, you need to disable the buzzer again.
Selecting the previous option: During the setting of UPS
parameters, press
ON/MUTE
for more than 3 seconds.
Release the button when you hear a beep sound to select the
previous option.
Transferring to battery self-check: In normal mode, ECO
mode, or frequency conversion mode, hold down
ON/MUTE
for more than 5 seconds to enter the battery
self-check test.
OFF/ENTER
Shutting down the UPS: Hold down
OFF/ENTER
for over
2 seconds to turn off the UPS in battery mode. If the UPS is
originally in normal mode, hold down this button will
enable the UPS to enter the standby mode or bypass mode
(if set or enabled before).
Confirming setting: During the setting of UPS parameters,
press
OFF/ENTER
for more than 3 seconds to confirm the
setting.
Manually clearing alarms: When an alarm that can be
manually cleared exists, hold down
OFF/ENTER
for over
2 seconds to manually clear the alarm.