UPS2000-G-(1 kVA-3 kVA)
User Manual (2016, Russia)
4 Setting Control Panel
Issue 02 (2016-07-28)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
32
Alarm
ID
Alarm
Cause
ID
Alarm
Name
Alarm
Severity
Alarm
Clear
Mode
Trigger
Condition
Impact on
the System
Repair Proposal
UPS fails to
start.
repair.
42
17
Interna
l fault
Critical
This alarm
must be
manually
cleared.
The bus
voltage is
higher than
450 V.
If this alarm is
generated
during the
running of the
UPS, the UPS
transfers to
bypass mode.
Possible cause:
The mains has
experienced a
transient high
voltage.
Measure: Rectify
the fault and
restart the UPS.
Possible cause:
The output
supplies power to
special loads
such as the
inductive and
rectification
loads.
Measure: Check
that the load
types are
supported by the
UPS.
Possible cause:
The hardware is
damaged.
Measure: Contact
the dealer or
Huawei technical
support.
42
18
Interna
l fault
Critical
This alarm
must be
manually
cleared.
The bus
voltage is
lower than
260 V.
If this alarm is
generated
during the
running of the
UPS, the UPS
transfers to
bypass mode.
Possible cause:
The hardware is
damaged.
Measure: Contact
the dealer or
technical
support.
Possible cause:
An overload
occurred when
the input voltage
was low.
Measure: Rectify
the fault and
restart the UPS.
42
24
Interna
Minor
This alarm
is
An error
occurs in
All UPS
parameters are
Possible cause: The