UPS2000-G-(1 kVA-3 kVA)
User Manual (2016, Russia)
4 Setting Control Panel
Issue 02 (2016-07-28)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
33
Alarm
ID
Alarm
Cause
ID
Alarm
Name
Alarm
Severity
Alarm
Clear
Mode
Trigger
Condition
Impact on
the System
Repair Proposal
l fault
automatic
ally
cleared.
the
EEPROM.
restored to the
factory
settings. If this
alarm is
generated, the
customer
needs to
replace the
UPS.
EEPROM is faulty.
Measure: Contact
the dealer or Huawei
technical support.
42
27
Interna
l fault
Critical
This alarm
must be
manually
cleared.
The
inverter
voltage is
higher than
1.15 times
the rated
output
voltage.
If this alarm is
generated
during the
running of the
UPS, the UPS
transfers to
bypass mode.
Possible cause: The
inverter is faulty.
Measure: Contact
the dealer or Huawei
technical support.
Interna
l fault
Critical
This alarm
must be
manually
cleared.
The
inverter
output
voltage is
lower than
75% of the
rated
output
voltage,
and the
output
current is
lower than
60% of the
rated
output
current.
If this alarm is
generated
during the
running of the
UPS, the UPS
transfers to
bypass mode.
42
28
Interna
l fault
Critical
The first
three
alarms are
cleared
automatic
ally. Later
alarms, if
generated,
must be
cleared
manually.
The
inverter
output
voltage is
lower than
100 V.
If this alarm is
generated
during the
running of the
UPS, the UPS
transfers to no
output. After
20 minutes,
the UPS
automatically
starts the
inverter. If this
alarm persists,
the UPS then
transfers to no
Possible cause:
The output load
types are not
supported or the
load exceeds the
specifications.
Measure: Check
whether the load
types are
supported and
reduce the output
load. Then,
manually clear
the alarm and