UPS2000-G-(1 kVA-3 kVA)
User Manual (2016, Russia)
9 Specifications
Issue 02 (2016-07-28)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
53
9
Specifications
Table 9-1
Rack-mounted UPS specifications
Specifications
1 kVA
2 kVA
3 kVA
Capacity
1000 VA/800 W
2000 VA/1600 W 3000 VA/2400 W
Input
Voltage
range
Lowest
conversio
n voltage
When the ambient temperature is 0–35°C:
160/140/120/110 V AC (tolerance ±5%)
(Ratio of actual load to rated load:
100%–80%/80%–70%/70%–60%/60%–0)
When the ambient temperature is 35–40°C:
175/155/135/125 V AC (tolerance ±5%)
(Ratio of actual load to rated load:
100%–80%/80%–70%/70%–60%/60%–0)
Lowest
recovery
voltage
When the ambient temperature is 0–35°C:
175/155/135/125 V AC (tolerance ±5%)
(Ratio of actual load to rated load:
100%–80%/80%–70%/70%–60%/60%–0)
When the ambient temperature is 35–40°C:
190/170/150/140 V AC (tolerance ±5%)
(Ratio of actual load to rated load:
100%–80%/80%–70%/70%–60%/60%–0)
Highest
conversio
n voltage
300 V AC (tolerance ±5%, load percentage < 80%)
280 V AC (tolerance ±5%, 80% < load percentage <
100%, after 15 minutes to battery mode)
Highest
recovery
voltage
290 V AC (tolerance ±5%, load percentage < 80%)
270 V AC (tolerance ±5%, 80% < load percentage <
100%)
Frequency range
40–70 Hz
Phase
Single-phase, grounded