UPS2000-G-(6 kVA-20 kVA)
User Manual
C Alarm Handling
Issue 13 (2019-05-05)
Copyright © Huawei Technologies Co., Ltd.
130
Alarm
ID
(Alarm
ID-Alar
m
Cause)
Alarm
Name
Alarm
Level
Alarm
Clear
Mode
Impact on the System
Repair Proposal
The UPS is in battery
self-check state.
The mains loading capability
is insufficient.
Measures:
Check the mains input. If the
mains input is abnormal, wait
until the mains input recovers.
Check whether the UPS is in
battery self-check state.
Reduce the load or replace the
UPS with a larger-capacity
UPS.
0340-01
Maint.
breaker
ON
Minor
Automati
c clear
The UPS transfers to
bypass mode.
Possible cause: The maintenance
circuit breaker is ON during UPS
maintenance.
Measure: Switch off the
maintenance circuit breaker after
maintenance.
61440-0
1
Flash
fault
Critical
Automati
c clear
Files may be damaged.
Possible cause: The flash
memory cannot be properly read
or written.
Measure: Contact Huawei
technical support for repair.