UPS2000-G-(6 kVA-20 kVA)
User Manual
C Alarm Handling
Issue 13 (2019-05-05)
Copyright © Huawei Technologies Co., Ltd.
117
Alarm
ID
(Alarm
ID-Alar
m
Cause)
Alarm
Name
Alarm
Level
Alarm
Clear
Mode
Impact on the System
Repair Proposal
of batteries meets
requirements.
Disconnected the external
battery charger, check
whether the alarm is cleared.
If not, contact Huawei
technical support for repair.
0034-01
Remaini
ng cap.
warning
Minor
Automati
c clear
If no action is taken,
continued discharge will
result in system shutdown
due to EOD.
Possible cause:
The battery discharge lasts too
long.
The mains input is abnormal.
The number of batteries or
battery capacity is incorrectly
set.
Measure:
Check the mains, and charge
batteries in a timely manner.
Check the configured battery
capacity.
0036-01
Batt.
maint.
notif
Minor
Automati
c clear
An alarm is generated. If
the shallow discharge test
is not performed for a long
time, the battery power
backup function may be
affected.
Possible cause: The battery does
not experience shallow discharge,
and the maintenance period
expires.
Measure:
Perform the following steps:
Click the alarm. The battery
maintenance menu is displayed.
Perform a shallow discharge test.
The alarm will be automatically
cleared no matter whether test
conditions are met.
0040-01
Rectifier
fault
Critical
Manual
clear/Po
wer-off
clear
The UPS shuts down.
The UPS transfers to
another working mode or
shuts down.
Possible cause: The soft-start
resistor is damaged.
Measure: Contact Huawei
technical support for repair.
0040-02
Rectifier
fault
Critical
Manual
clear/Po
wer-off
clear
The UPS cannot be started. Possible causes:
The mains input harmonic is
large.
The rectifier startup circuit is
damaged.