UPS2000-G-(6 kVA-20 kVA)
User Manual
B LCD Menus and Parameters
Issue 13 (2019-05-05)
Copyright © Huawei Technologies Co., Ltd.
107
Main
Menu
Second-
Level
Menu
Third-Level
Menu
Fourth-Level
Menu
Value Range
Preset Value
long backup time
model.
For the
UPS2000-G-15
kVA/20 kVA, the
default value is
65 Ah
on a long backup time
model.
Intelli.
Hibernation
Enabled and Disabled
Disabled
Overtemp.
thres.
45–55°C
50°C
Undertemp.
thres.
–30°C to +5°C
–5°C
Overcurrent
thres.
2.0–4.0 A (standard
model)
4.0–8.0 A (long
backup time model)
3.0 A (standard
model)
6.0 A (long backup
time model)
Equalized
Charge
Equalized
charging
Enabled and Disabled
Enabled
Time interval
30–180 days
60 Day
Voltage
2.33–2.40 V/cell
2.35 V/cell
Max. current
1.0–2.0 A (standard
model)
1.0–4.0 A (long
backup time model)
2.0 A
Max. time
600–999 minutes
960 Min
Float Charge
Voltage
2.25–2.30 V/cell
2.25 V/cell
Temp. comp.
coef.
0.0–6.0 mV/°C*cell
3.3 mV/°C*cell
Discharge
Max. time
(configurable
in non-battery
mode)
0–24 hours
16 Hour
EOD mode
(configurable
in non-battery
mode)
Batt. protect first, Backup
time first, and Balanced
mode
Backup time first
EOD auto-start
(configurable
Enabled and Disabled
Enabled