UPS2000-G-(6 kVA-20 kVA)
User Manual
C Alarm Handling
Issue 13 (2019-05-05)
Copyright © Huawei Technologies Co., Ltd.
121
Alarm
ID
(Alarm
ID-Alar
m
Cause)
Alarm
Name
Alarm
Level
Alarm
Clear
Mode
Impact on the System
Repair Proposal
output because bypass
cables for the newly added
UPS are incorrectly
connected.
0042-12
Internal
fault
Critical
Manual
clear/Po
wer-off
clear
The UPS startup is not
allowed.
Possible cause: The three-phase
power cable lengths vary greatly.
Measure: Ensure that the lengths
of three-phase power cables vary
within a difference of 5%.
0042-13
Internal
fault
Critical
Manual
clear/Po
wer-off
clear
The UPS startup is not
allowed.
Possible cause: The inverter is
faulty.
Measure: Contact Huawei
technical support for repair.
0043-01
Fan fault
Critical
Automati
c clear
The power supply from the
UPS and system is not
affected.
Possible cause: The fan is
abnormal.
Measure: Clean off the foreign
objects around the fan. If the
alarm persists, contact Huawei
technical support for repair.
0043-06
Fan fault
Critical
Automati
c clear
The power supply from the
UPS and system is not
affected.
Possible cause: The fan is
abnormal.
Measure: Clean off the foreign
objects around the fan. If the
alarm persists, contact Huawei
technical support for repair.
0044-01
Incompat
ible ver.
Critical
Manual
clear/Po
wer-off
clear
The UPS startup is not
allowed.
Possible cause: An error occurred
during software loading.
Measure: Contact the
manufacturer to load software.
0044-02
Incompat
ible ver.
Critical
Manual
clear/Po
wer-off
clear
The UPS startup is not
allowed.
Possible cause: Software and
hardware versions do not match.
Measure: Contact the
manufacturer to load software.
0044-03
Incompat
ible ver.
Critical
Manual
clear/Po
wer-off
clear
The UPS startup is not
allowed.
Possible cause: Software and
hardware versions do not match.
Measure: Contact the
manufacturer to load software.
0044-04
Incompat
ible ver.
Critical
Manual
clear/Po
wer-off
The UPS startup is not
allowed.
Possible cause: An error occurred
during software loading.
Measure: Contact the