UPS2000-G-(6 kVA-20 kVA)
User Manual
C Alarm Handling
Issue 13 (2019-05-05)
Copyright © Huawei Technologies Co., Ltd.
122
Alarm
ID
(Alarm
ID-Alar
m
Cause)
Alarm
Name
Alarm
Level
Alarm
Clear
Mode
Impact on the System
Repair Proposal
clear
manufacturer to load software.
0044-05
Incompat
ible ver.
Critical
Manual
clear/Po
wer-off
clear
The UPS startup is not
allowed.
Possible cause: Software and
hardware versions do not match.
Measure: Contact the
manufacturer to load software.
0044-06
Incompat
ible ver.
Critical
Manual
clear/Po
wer-off
clear
The UPS startup is not
allowed.
Possible cause: Software and
hardware versions do not match.
Measure: Contact the
manufacturer to load software.
0045-03
Charger
alarm
Critical
Manual
clear/Po
wer-off
clear
The charger in the UPS
stops.
Possible cause: The charger
capacitor is faulty.
Measure: Contact Huawei
technical support for repair.
0045-04
Charger
alarm
Critical
Possible cause: The charger
output is short-circuited.
Measure: Rectify battery port
short circuits. After you clear the
alarm, restart the UPS. If the
alarm persists, contact Huawei
technical support for repair.
0045-06
Charger
alarm
Critical
Possible cause: The charger is
faulty.
Measure: Contact Huawei
technical support for repair.
0045-07
Charger
alarm
Critical
Manual
clear/Po
wer-off
clear
The charger in the UPS
stops.
(The 20 kVA has no
action.)
Possible cause: The charger is
faulty.
Measure: Contact Huawei
technical support for repair.
0045-08
Charger
alarm
Critical
Manual
clear/Po
wer-off
clear/Aut
omatic
clear
The charger in the UPS
stops.
0045-09
Charger
alarm
Critical
Manual
clear/Po
wer-off
clear
0045-10
Charger
alarm
Critical