UPS2000-G-(6 kVA-20 kVA)
User Manual
B LCD Menus and Parameters
Issue 13 (2019-05-05)
Copyright © Huawei Technologies Co., Ltd.
105
Main
Menu
Second-
Level
Menu
Third-Level
Menu
Fourth-Level
Menu
Value Range
Preset Value
220 V, 230 V, and
240 V, single-phase
(on the
UPS2000-G-15
kVA/20 kVA)
380 V, 400 V, and
415 V, three-phase
(on the
UPS2000-G-15
kVA/20 kVA)
(on the
UPS2000-G-15
kVA/20 kVA)
380 V, three-phase
(on the
UPS2000-G-15
kVA/20 kVA)
Frequency
level
50 Hz, 60 Hz, and
Automatic
50 Hz
Volt. adj. coef.
±5%, ±4%, ±3%, ±2%,
±1%, and 0%
0%
Converter
mode
Enabled and Disabled
Disabled
Bypass
(configurable
after the
inverter shuts
down)
Max. voltage
10%, 15%, 20%, 25%,
and 30%
15%
Min. voltage
10%, 20%, 30%, 40%,
50%, and 60%
20%
Frequency
range
±0.5 Hz, ±1 Hz, ±2 Hz,
±3 Hz, ±4 Hz, ±5 Hz, and
±6 Hz
±2 Hz
ECO
(configurable
after the
inverter shuts
down)
Max. voltage
5%, 6%, 7%, 8%, 9%,
and 10%
10%
Min. voltage
5%, 6%, 7%, 8%, 9%,
and 10%
10%
Frequency
range
±0.5 Hz, ±1 Hz, ±2 Hz,
and ±3 Hz
±2 Hz
Single UPS
ECO
Enabled and Disabled
Disabled
Power
segment
Dis. time thres.
(configurable
in non-battery
mode)
0–999 minutes
30 Min
Dis. volt. thres.
(configurable
in non-battery
mode)
1.90–2.25 V/cell
2.00 V/cell
Power Segment
(configurable
Enabled and Disabled
Disabled