UPS2000-G-(6 kVA-20 kVA)
User Manual
C Alarm Handling
Issue 13 (2019-05-05)
Copyright © Huawei Technologies Co., Ltd.
125
Alarm
ID
(Alarm
ID-Alar
m
Cause)
Alarm
Name
Alarm
Level
Alarm
Clear
Mode
Impact on the System
Repair Proposal
0061-02
Inverter
alarm
Minor
Manual
clear/Po
wer-off
clear
N/A
Possible cause: The EEPROM
chip is faulty.
Measure: Contact Huawei
technical support for repair.
0064-01
OL
timeout
Critical
Automati
c clear
The UPS automatically
starts after shutdown.
The UPS transfers to
another working mode or
shuts down.
Possible cause: The load exceeds
the rated inverter loading
capacity.
Measure: Reduce the load or
replace the UPS with a
larger-capacity UPS.
0064-02
OL
timeout
Critical
Manual
clear/Po
wer-off
clear
The UPS startup is not
allowed.
Possible cause: The load exceeds
the rated bypass loading capacity.
Measure: Reduce the load or
replace the UPS with a
larger-capacity UPS.
0065-01
Power
segment
Minor
Manual
clear/Po
wer-off
clear
In single UPS mode, the
loads connected to pL
power off.
Possible cause: The load exceeds
the rated loading capacity.
Measure: Reduce the load or
replace the UPS with a
larger-capacity UPS.
0065-02
Power
segment
Minor
Automati
c
clear/Ma
nual
clear
Possible causes:
The battery voltage is below
the battery protection voltage.
The battery discharge time
exceeds the battery protection
time.
Measures:
Check the battery voltage.
Modify the power segment
settings on the LCD.
0066-01
Output
overload
Minor
Automati
c clear
Continuous overload
causes the UPS to transfer
to bypass mode or supply
no power.
Possible cause: The load exceeds
the rated loading capacity.
Measure: Reduce the load or
replace the UPS with a
larger-capacity UPS.
0066-02
Output
overload
Minor
Automati
c clear
Continuous overload
causes the UPS to supply
no power.
Possible cause: The load exceeds
the rated bypass loading capacity.
Measure: Reduce the load or
replace the UPS with a