UPS2000-G-(6 kVA-20 kVA)
User Manual
C Alarm Handling
Issue 13 (2019-05-05)
Copyright © Huawei Technologies Co., Ltd.
127
Alarm
ID
(Alarm
ID-Alar
m
Cause)
Alarm
Name
Alarm
Level
Alarm
Clear
Mode
Impact on the System
Repair Proposal
alarm is cleared.
0086-01
BPS
trans.
overlimit
Minor
Manual
clear/Po
wer-off
clear
Transfer to an unstable
side is not allowed.
Possible cause: The output
transfer times within 30 minutes
exceed the configured value (3 by
default).
Measure: Restart the UPS after
the alarm is cleared.
0094-01
Redunda
ncy
failure
Minor
Automati
c clear
N/A
Possible causes:
The configured number of
redundant UPSs exceeds the
maximum allowed value.
The load exceeds the rated
loading capacity of the
requisite UPSs in the parallel
system.
Measures:
Reduce the number of
redundant UPSs or set the
system to be non-redundant.
Reduce the load or replace the
UPS with a larger-capacity
UPS.
0096-01
Abnorma
l ECO
volt.
Minor
Automati
c clear
Transfer to bypass mode is
prohibited. If the bypass is
supplying power, the UPS
transfers to another
working mode.
Possible cause: The ECO input is
abnormal.
Measure: Check whether the
ECO input voltage or frequency
exceeds the configured range. If
yes, change the range or wait
until the bypass input recovers.
0105-05
Comm.
failed.
Minor
Automati
c clear
The monitoring module
cannot monitor the digital
signal processor (DSP) of
the power module.
Possible causes:
The communications cable is
faulty.
An internal fault occurs in the
UPS.
Measures:
Check the communications
cable.
Contact Huawei technical
support for repair.
0125-01
Incon.
Critical
Automati
An alarm is generated, and
Possible cause: The parallel