Alarm
ID
Alarm Name
Alarm
Severity
Possible Causes
Troubleshooting
2034
Grid
Overvoltage
Major
Cause ID = 1
The grid voltage exceeds
the higher threshold or the
high voltage has lasted for
more than the value
specified by high voltage
ride-through (HVRT).
1. If the alarm occurs
occasionally, the power
grid may be abnormal
temporarily. The
SUN2000 automatically
recovers after detecting
that the power grid
becomes normal.
2. If the alarm occurs
frequently, check
whether the power grid
voltage is within the
allowed range. If no,
contact the local power
operator. If yes, modify
the grid overvoltage
protection threshold
through the mobile app,
SmartLogger, or NMS
with the consent of the
local power operator.
3. Check whether the peak
voltage of the power
grid is too high. If the
fault persists and cannot
be rectified for a long
time, contact the power
operator.
SUN2000-(2KTL-6KTL)-L1
User Manual
8 System Maintenance
Issue 04 (2021-04-01)
Copyright © Huawei Technologies Co., Ltd.
85