Table 7-1 Grid-tied point control
Parameter Name
Description
Active
power
Unlimited
-
If this parameter is set to Unlimited,
the output power of the SUN2000 is
not limited and the SUN2000 can
connect to the power grid at the
rated power.
Grid connection
with zero power
Closed-loop controller
● If multiple SUN2000s are
cascaded, set this parameter to
SDongle/SmartLogger.
● If there is only one SUN2000, set
this parameter to Inverter.
Limitation mode
Total power indicates export
limitation of the total power at the
grid-tied point.
Power adjustment
period
Specifies the shortest interval for a
single anti-backfeeding adjustment.
Power control
hysteresis
Specifies the dead zone for adjusting
the SUN2000 output power. If the
power fluctuation is within the power
control hysteresis, the power is not
adjusted.
Active power output
limit for fail-safe
Specifies the derating value of the
SUN2000 active power by percentage.
If the Smart Dongle does not detect
any meter data or the
communication between the Smart
Dongle and the SUN2000 is
disconnected, the Smart Dongle
delivers the derating value of the
SUN2000 active power by percentage.
Communication
disconnection fail-safe
In the SUN2000 anti-backfeeding
scenario, if this parameter is set to
Enable, the SUN2000 will derate
according to the active power
derating percentage when the
communication between the
SUN2000 and the Smart Dongle is
disconnected for a period longer than
Communication disconnection
detection time.