PDU8000 Modular Precision PDC V2.0
User Manual
8 Maintenance Guide
Issue 03 (2018-01-25)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
137
Fuse No.
Function
1FU15/2FU15
Voltage sampling fuse of phase L1 on the power board to the right of the
third output subrack (cabinet rear view)/Voltage sampling fuse of phase
L3 on the power board to the left of the third output subrack (cabinet rear
view)
The preceding tables use a fully configured PDC as an example. The actual cabinet configurations
prevail.
*FU*-1 indicates the fuse input end, and *FU*-2 indicates the fuse output end.
Procedure
Step 1
Push the fuse handle up outwards.
Step 2
Remove the faulty fuse.
Figure 8-17
Removing a fuse
Step 3
Install a new fuse, and reinstall the handle.
----End
8.4.6 Replacing a monitoring board
Prerequisites
Tool: Phillips screwdriver
Materials: new monitoring board