7 MDU Commissioning Guide
Issue 03 (2018-01-25)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
93
Automatic: The MDU automatically queries available IP addresses in the
connected network. Ensure that the MDU and PC are on the same network
segment.
You can set IP address allocation to
Manual
or
Automatic
. If the MDU restarts, IP address allocation
automatically changes to
Automatic
. The IP address is bound as the IP address set last time, allowing
you to log in for the second time.
IP address
Set an IP address for the Ethernet. The value ranges from 0.0.0.0 to 255.255.255.255. The
default value is
192.168.0.10
.
Ensure that the IP address is unique on the network segment. Otherwise, the LCD cannot
work properly.
Subnet mask
Set a subnet mask for the Ethernet. The value ranges from 0.0.0.0 to 255.255.255.255. The
default value is
255.255.255.0
.
Gateway
Set an Ethernet gateway. The value ranges from 0.0.0.0 to 255.255.255.255. The default value
is
192.168.0.1
.
Serial port baud rate
Set the serial port communications rate. The value options include 4800, 9600, and 19200.
The default value is
9600
.
Serial port address
Set the serial port communications address. The value ranges from 0 to 254. The default value
is
1
.
SSL
Indicates whether Modbus-TCP supports encryption transmission. The default value is
Enable
.
ModbusTCPcertification
Sets the secondary authentication for NMS access. The default value is
Disable
.
SNMP Configuration
Set SNMP related parameters.
7.4.3.3 System Parameter Settings
On the
Settings
screen, tap
System Param.
to access the screen.