4.1 DC Power Cables
This section describes the structure and technical specifications of the DC-input power cable.
CAUTION
If no special requirements are imposed on power cables, power cables are delivered according
to default configurations. Otherwise, power cables need to be purchased locally. For rules of
selecting power cables, refer to the corresponding computation formula in
Power Distribution
Guide
.
If a power cable longer than 35 m ( 114.83 ft ) is needed, you need to deploy a Power Distribution
Frame (PDF) near the device.
The specifications of the power cable to be delivered are determined by the power distribution
distance (the distance between the Router and the Power Distribution Frame) that is surveyed.
6 mm^2 ( 0.009 in.^2 ) Power Cable
describes the specifications of the 6 mm^2 ( 0.009 in.^2 ) power cable.
Table 4-1
Terminal and cable specifications of the 6 mm^2 ( 0.009 in.^2 ) power cable
Item
Description
Terminal
Naked Crimping Terminal,OT,6mm^2,M6,Tin Plating,Naked Ring
Terminal
Naked Crimping Terminal,OT,6mm^2,M8,Tin Plating,Naked Ring
Terminal
Cable
Power Cable,-450/750V,H07Z-K UL3386,6mm^2,Blue,Low Smoke Zero
Halogen Cable
Power Cable,-450/750V,H07Z-K UL3386,6mm^2,Black,Low Smoke Zero
Halogen Cable
10 mm^2 ( 0.02 in.^2 ) Power Cable
describes the specifications of the 10 mm^2 ( 0.02 in.^2 ) power cable.
Table 4-2
Terminal and cable specifications of the 10 mm^2 ( 0.02 in.^2 ) power cable
Item
Description
Terminal
Naked Crimping Terminal,OT,10mm^2,M6,Tin Plating,Naked Ring
Terminal
HUAWEI NE40E-X1 & NE40E-X2 Universal Service
Router
Hardware Description
4 Cables
Issue 02 (2011-09-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
74