74
LP-171 Rev. 3.3.15
HEATER START-UP REPORT
LIGHT OFF ACTIVITIES
DATE COMPLETED ________________
1) Fill the
heating system
Check all piping and gas connections, verify all
are tight
Pressurize system (12-15 PSI)
____ PSI
Add water to prime condensate cup
What percentage of propylene glycol is
installed in the system (0-50%)
____ %
Verify near heater piping is properly supported
2) Check gas
pipe
Leak test using locally approved methods
(consult jurisdictional code book)
Check incoming gas pressure (3.5” to 14”
W.C.)
____ in w.c.
Static
What is the “drop” on light off (No more than 1”
W.C.)
____ in w.c.
Dynamic
3) Check
combustion
Check and adjust (if necessary) carbon
dioxide content
____% CO2
High Fire
____% CO2
Low Fire
Check and adjust (if necessary) carbon
monoxide content
____ppm CO
High Fire
____ ppm CO
Low Fire
4) Verify
system
operation
Turn up thermostat to verify wiring connections
5) Record
ionization
current
Check uA reading at d7 on the status menu
(see start-up section)
____ uA
High Fire
____ uA
Low Fire
6) Record
system settings
Record heating curve (with optional Vision
One kit, record steps)
____*8
____*9
____*10
____*11
7) Indirect
water heater
Verify safety and operation of the indirect
water heater, record settings
____de
____dh
8) Convert the
heater
If necessary, convert the heater to the proper
gas type
Locate the stickers in the appropriate locations
on the heater
Verify combustion settings after gas
conversion, Carbon Dioxide
____% CO2
High Fire
____% CO2
Low Fire
Verify combustion settings after gas
conversion, Carbon Monoxide
____ppm CO
High Fire
____ppm CO
Low Fire
Mail in the conversion registration
Notes:
Table 18
MAINTENANCE REPORT
In unusually dirty or dusty conditions, care must be taken to keep heater cabinet door in place at all times. Failure to do so VOIDS
WARRANTY!
Allowing the heater to operate with a dirty combustion chamber will hurt operation. Failure to clean the heat exchanger as needed by
the installation location could result in heater failure, property damage, personal injury, or death. Such product failures ARE NOT
covered under warranty.
The heater requires minimal periodic maintenance under normal conditions. However, in unusually dirty or dusty conditions, periodic
vacuuming of the cover to maintain visibility of the display and indicators is recommended.
Periodic maintenance should be performed once a year by a qualified service technician to assure that all the equipment is operating
safely and efficiently. The owner should make necessary arrangements with a qualified heating contractor for periodic maintenance of
the heater. Installer must also inform the owner that the lack of proper care and maintenance of the heater may result in a hazardous
condition.
Summary of Contents for MC120
Page 21: ...21 LP 171 Rev 3 3 15 M PIPING DETAILS Figure 5 ...
Page 53: ...53 LP 171 Rev 3 3 15 Figure 30 ...
Page 71: ...71 LP 171 Rev 3 3 15 Figure 34 ...
Page 72: ...72 LP 171 Rev 3 3 15 Figure 35 ...
Page 73: ...73 LP 171 Rev 3 3 15 Figure 36 ...
Page 76: ...76 LP 171 Rev 3 3 15 ...
Page 77: ...77 LP 171 Rev 3 3 15 ...