92
MAINTENANCE REPORT
In unusually dirty or dusty conditions, care must be taken to keep boiler cabinet door in place at all times. Failure
to do so VOIDS WARRANTY!
Allowing the boiler to operate with a dirty combustion chamber will hurt operation. Failure to clean the heat
exchanger as needed by the installation location could result in boiler failure, property damage, personal injury, or
death. Such product failures ARE NOT covered under warranty.
The boiler requires minimal periodic maintenance under normal conditions. However, in unusually dirty or dusty
conditions, periodic vacuuming of the cover to maintain visibility of the display and indicators is recommended.
Periodic maintenance should be performed once a year by a qualified service technician to assure that all the
equipment is operating safely and efficiently. The owner should make necessary arrangements with a qualified
heating contractor for periodic maintenance of the boiler. Installer must also inform the owner that the lack of
proper care and maintenance of the boiler may result in a hazardous condition.
INSPECTION ACTIVITIES
DATE LAST COMPLETED
PIPING
1
st
YEAR
2
nd
YEAR
3
rd
YEAR
4
th
YEAR*
Near boiler piping
Check boiler and system piping for any sign of
leakage. Continual fresh make-up water will reduce
boiler life. Leaking pipes could cause property
damage. Make sure all piping is properly supported.
Vent
Check condition of all vent pipes and joints. Ensure all
vent piping is properly supported. Check for
obstructions at intake and exhaust termination points.
Gas
Check Gas piping, test for leaks and signs of aging.
Make sure all pipes are properly supported.
SYSTEM
Visual
Do a full visual inspection of all system components.
Functional
Test all functions of the system (Heat, Safeties)
Temperatures
Verify safe settings on boiler or Anti-Scald Valve
Temperatures
Verify programmed temperature settings
ELECTRICAL
Connections
Check wire connections. Make sure they are tight.
Smoke and CO
detector
Verify devices are installed and working properly.
Change batteries if necessary.
Circuit Breakers
Check to see that the circuit breaker is clearly labeled.
Exercise circuit breaker.
Switch and Plug
Verify ON/OFF switch and convenience plug are both
functional
CHAMBER/BURNER
Combustion Chamber
Check burner tube and combustion chamber coils.
Clean according to maintenance section of manual.
Vacuum combustion chamber.
Spark Electrode
Clean. Set gap at ¼”.
Flame Probe
Clean. Check ionization in uA (d7 on status menu in
Start-up Procedures). Record high fire and low fire.
CONDENSATE
Neutralizer
Check condensate neutralizer. Replace if necessary.
Condensate hose
Disconnect condensate hose. Clean out dirt. Fill with
water to level of outlet and re-install. (NOTE: Verify
the flow of condensate, making sure that the hose is
properly connected during final inspection.)
GAS
Pressure
Measure incoming gas pressure (
3.5” to 14” W.C.)
Pressure Drop
Measure drop in pressure on light off (no more than 1”
W.C.)
Summary of Contents for EL-110
Page 15: ...15 Figure 3 ...
Page 61: ...61 Figure 29 ...
Page 62: ...62 Figure 30 ...
Page 87: ...87 Figure 33 ...
Page 88: ...88 Figure 34 ...
Page 89: ...89 Figure 35 LP 293 A NOTE Parts listed on the following page ...
Page 94: ...94 ...
Page 95: ...95 ...
Page 96: ...96 MAINTENANCE NOTES ...