COMBI521
EN - 95
16.
For single-phase EVSE systems
, press the
GO/STOP
key on the instrument. The instrument starts the
automatic test sequence of insulation resistance among
L-N, L-PE and N-PE respectively, and displays the
message "
Measuring...
". The instrument displays the
message "
OK
" in case of a positive result of every test
(value higher than the set minimum threshold).
M
15/10 – 18:04
RL-N
>
999 M
Vt
=
523 V
RL-PE = 250 M
Vt = 525 V
RN-PE > 999 M
Vt = 524 V
OK
AUTO 500V 1.00M
MODE
Vtest Lim.
17.
Press the
SAVE
key to partially save the test, and to carry on with the subsequent test
(no. 26).
18.
For three-phase EVSE systems
, press the
GO/STOP
key on the instrument.
The instrument starts the
automatic test sequence of insulation resistance between
L1-N
and
L1-PE
respectively, and displays the message
"
Measuring...
".
The instrument displays the message
"
Connect phase L2
" in case of a positive result of the
tests (value higher than the set minimum threshold).
Press the
SAVE
key to partially save the test, and to
carry on with the test on Phase L2. The following screen
appears on the display:
M
15/10 – 18:04
RL1-N >
999 M
Vt = 514 V
RL1-PE > 999 M
Vt = 511 V
RL2-N =
- - - M
Vt = - - - V
RL2-PE = - - - M
Vt = - - - V
RL3-N =
- - - M
Vt = - - - V
RL3-PE = - - - M
Vt = - - - V
RN-PE = - - - M
Vt = - - - V
Connect phase L2
AUTO 500V 1.00M
MODE
Vtest Lim.
19. Connect the instrument to the adapter as shown in the
diagram on the display (input
B4
to input
N
, input
B3
to
input
E
and input
B1
to input
L2
).
Use the three
selectors of the adapter and set the following
positions
:
PP State
NC
CP State
A
Fault
OK
M
15/10 – 18:04
2/6 – L2 Insulation test
20. Press the
GO/STOP
key on the instrument. The
instrument starts the automatic test sequence of
insulation resistance between
L2-N
and
L2-PE
respectively, and displays the message "
Measuring...
".
The instrument displays the message "
Connect phase
L3
" in case of a positive result of the tests (value higher
than the set minimum threshold).
Press the
SAVE
key to partially save the test, and to
carry on with the test on Phase L3. The following screen
appears on the display:
M
15/10 – 18:04
RL1-N >
999 M
Vt = 514 V
RL1-PE > 999 M
Vt = 511 V
RL2-N =
250 M
Vt = 517 V
RL2-PE > 999 M
Vt = 514 V
RL3-N =
- - - M
Vt = - - - V
RL3-PE = - - - M
Vt = - - - V
RN-PE = - - - M
Vt = - - - V
Connect phase L3
AUTO 500V 1.00M
MODE
Vtest Lim.