COMBI521
EN - 105
58. Connect the instrument to the adapter as shown in the
diagram on the display (input
B4
to input
N
, input
B3
to
input
E
and input
B1
to input
L1
).
Use the three
selectors of the adapter and set the following
positions:
PP State
13A,20A,32A
or
63A
CP State
C
Fault
E
NOTE: some EVSE stations may not be able to
manage this fault condition. In this case, leave the
Fault selector in position PE to carry out this test.
STS
15/10 – 18:04
3/6 – Checking FAULT E
59. Press the
GO/STOP
key to start the test
on E status
.
The following screen appears on the display. Notice the
presence of the status “
FAULT E
” corresponding to the
position “STATUS”.
STS
15/10 – 18:04
L1-N
= - - - V CP = - - - V
L1-PE
= - - - V F
= - - - Hz
N-PE
= - - - V I
= - - - A
FAULT E
STATUS
60. Press the
GO/STOP
key. The result of measurements is
shown in the screen on the side. The instrument
displays the message "
OK
" in case of a positive result of
the tests (see Table 3: List of considered situations
when checking statuses
).
STS
15/10 – 18:04
L1-N
= 0 V CP = 11 V
L1-PE
= 0 V F
= 0 Hz
N-PE
= 0 V I
= 0.0 A
OK
FAULT E
STATUS
61.
Press the
SAVE
key to end the test
on status check, save the final result in the
instrument's memory and go on to the subsequent test (no. 64).
62. The instrument displays the message "
FAIL
" in case of a
negative result of at least one test (see Table 3)
STS
15/10 – 18:04
L1-N
= 19.6 V CP = 11 V
L1-PE = 4 V F
= 0 Hz
N-PE = 0 V I
= 0.0 A
FAIL
FAULT E
STATUS