6. Press the
GO/STOP
key. The screen on the side appears
on the display. The RPE test is carried out by the
instrument
only in STD mode
.
Set the limit threshold value
and calibrate the test leads as shown in § 6.3.
RPE
15/10 – 18:04
R
I t e s t
=
=
- - -
- - - m A
STD
2.00
- - -
MODE
Lim
>
<
7. Select mode
>
<
to compensate the resistance of the test leads as indicated in §
6.3.2.
CAUTION
Before connecting the test leads, make sure that there is no voltage at
the ends of the conductor to be tested.
Always make sure, before any measurement, that the compensation
resistance value is referred to the cables currently used. In case of
doubt, repeat the calibration procedure described in § 6.3.2.
8. Press the
GO/STOP
key. The instrument will start the measurement.
CAUTION
The message “
Measuring…
” appears on the display, to indicate that
measurement is in progress. During this whole stage, do not disconnect
the test leads of the instrument from the system being tested.
9.
At the end of measurement, the instrument shows the
message “
OK
” in case of a positive result (value lower than
the set limit threshold).
RPE
15/10 – 18:04
R
I t e s t
=
=
0 . 2 2
2 1 2 m A
OK
STD
2.00
0.21
MODE
Lim
>
<
10.
Press the
SAVE
key to partially save the test, and to carry on with the subsequent test
(no. 13).
11. At the end of the measurement, if the value of the
measured resistance is higher than the set limit, the
message “
FAIL
” is shown on the display.
RPE
15/10 – 18:04
R
I t e s t
=
=
4 . 5 4
2 1 2 m A
FAIL
STD
2.00
0.21
MODE
Lim
>
<