44. The instrument displays the message "
FAIL
" in case of a
negative result of at least one test (see Table 3)
STS
15/10 – 18:04
L1-N
= 195 V CP = 6.0 V
L1-PE = 230 V F
= 1000 Hz
N-PE = 0 V I
= 13.0 A
NO OK
C
STATUS
45. Press the
SAVE
key to partially save the test and to
end
the sequence of tests
. The instrument shows the
message contained in the following screen for a few
seconds.
Repeat the sequence again, if necessary.
STS
15/10 – 18:04
Sequence completed
C
STATUS
46.
In case of an EVSE system in a non-ventilated
environment (Vent = OFF)
, connect the instrument to
the adapter as shown in the diagram on the display (input
B4
to input
N
, input
B3
to input
E
and input
B1
to input
L1
).
Use the three selectors of the adapter and set the
following positions:
PP State
13A,20A,32A
or
63A
CP State
D
Fault
OK
NOTE: the EVSE station should have the possibility
to manually or automatically activate the forced
ventilation system.
STS
15/10 – 18:04
3/6 – Checking status D
47. Press the
GO/STOP
key. The following screen appears
on the display. Notice the presence of the status “
D
”
corresponding to the position “STATUS”
STS
15/10 – 18:04
L1-N
= - - - V CP = - - - V
L1-PE
= - - - V F
= - - - Hz
N-PE
= - - - V I
= - - - A
D
STATUS