COMBI521
EN - 101
39. Press the
SAVE
key to partially save the test and to
end
the sequence of tests
. The instrument shows the
message contained in the following screen for a few
seconds.
Repeat the sequence again, if necessary.
STS
15/10 – 18:04
Sequence completed
B
STATUS
40.
In case of an EVSE system in a non-ventilated
environment (Vent = OFF)
, connect the instrument to
the adapter as shown in the diagram on the display (input
B4
to input
N
, input
B3
to input
E
and input
B1
to input
L1
).
Use the three selectors of the adapter and set the
following positions:
PP State
13A,20A,32A
or
63A
CP State
C
Fault
OK
STS
1 5/10 – 18:04
3/6 – Checking status C
41. Press the
GO/STOP
key. The following screen appears
on the display. Notice the presence of the status “
C
”
corresponding to the position “STATUS”
STS
15/10 – 18:04
L1-N
= - - - V CP = - - - V
L1-PE
= - - - V F
= - - - Hz
N-PE
= - - - V I
= - - - A
C
STATUS
42. Press the
GO/STOP
key. The result of measurements is
shown in the screen on the side. The instrument displays
the message "
OK
" in case of a positive result of the tests
(see Table 3).
STS
15/10 – 18:04
L1-N
= 230 V CP = 6.0 V
L1-PE
= 230 V F
= 1000 Hz
N-PE
= 0 V I
= 13.0 A
OK
C
STATUS
43.
Press the
SAVE
key to partially save the test, and to carry on with the subsequent test
(no. 46).