CAUTION
Possible additional earth connections could influence the measured value. In
case of real difficulty in removing them, we recommend performing the
measurement in an indirect way.
5.
Press the
GO/STOP
key to start measurement. The
instrument shows the message "
Measuring...
" on the
display and continuously, in real time, the values of
current, and the maximum value detected, which is
constantly updated.
Press the
GO/STOP
key again to stop measurement.
The message "
OK
" appears in case of
positive
result
(the maximum value of current is lower than the set
limit threshold), further to the indication of the
date/time in which the maximum value was detected.
LEAK
15/10 – 18:04
M A X = 1 2 m A
1
m A
1 5 / 1 0 / 2 1 6 : 0 4 : 3 5
P M
OK
1A
30mA
FS
Lim.
6.
The message "
NO OK
" appears in case of
negative
result (the maximum value of current is higher than
the set limit threshold), further to the indication of the
date/time in which the maximum value was detected.
LEAK
15/10 – 18:04
M A X = 5 2 m A
1
m A
1 5 / 1 0 / 2 1 6 : 0 4 : 3 5
P M
NO OK
1A
30mA
FS
Lim.
7. Press the
SAVE
key to store the test result in the instrument’s memory (see §
7.1
) or
the
ESC/MENU
key to exit the screen without saving and go back to the main menu