WFS 1545 Operations Manual
iii.
F5 OVR (Alarm Override)
Pressing the F5 Button will call up the Alarm Override screen. Touching the ALARM
OVERRIDE button permits the pumps and chiller to operate with a Class 1 alarm condition.
It also toggles the image to CANCEL ALARM OVERRIDE.
Alarm Override prevents nuisance tripping during start up when the reservoirs may get low
prior to completely filling the system and reaching water flow equilibrium. The override
mode also allows operation should the leak sensor strip become wet during a filter element
change out.
The Alarm Override is canceled when the Cancel Alarm Override button is touched.
Additionally it will clear itself after 10 minutes if not manually canceled.
While operating in the Alarm Override mode the alarm tone will sound and the beacon will
pulse for 3 seconds once every minute as a reminder that the system is operating while in
override mode.
CAUTION: Maintain increased diligence!
While operating the system in the ALARM OVERRIDE mode the
pumps can be damaged by operating with low water.