29
WFS 1545 Operations Manual
With the Bypass valve fully open the reading on
process gauges do not include pressure increases
caused by the overall system. This provides a more
accurate reading of the increase caused by the filter
pressure. Close the bypass valve to bring the
process cooling loop back on-line.
Filter change out is recommended when the
pressure increase through the filter housing exceeds
50 PSI.
CAUTION:
There is no water flow to the process with the
Bypass Valve open to reservoir.
BYPASS VALVE