12
WFS 1545 Operations Manual
WARNING
: The control panel is heavy and awkward. Use proper equipment and caution when
lifting.
Remove the bolts from the top two spring nuts.
Loosen the bolts on the bottom spring nuts about
5/16”. Do not remove them. The bottom spring
nuts should be 14” apart with the rightmost nut
near the right end of the strut channel.
Lift the control cabinet over the lower bolts and
slide the bottom mounting tabs over the bolts. Let
the bottom bolts support the weight and bolt the
top tabs to the top spring nuts. Tighten all four
bolts.
Connect the yellow power cord to the round receptacle
on the bottom of the Control Panel.
Note: Connect any sensor cables that may
have been unplugged.
g.
ELECTRICAL CONNECTION
WARNING!:
•
Accidental contact with electrically live components can cause serious injury or death.
•
Always disconnect electrical power from source and lock out/tag out when working inside
the Control Panel
•
Only trained and qualified personnel may open the Control Panel
CAUTION:
Installation wiring must comply with local and national electrical codes.
The unit requires three (3) phase 220 VAC 60 Hz 30 Amp or 230 VAC 50 Hz 30 Amp power with
grounding wire.
Connect yellow power cord from
chiller to the Control Panel
Slide bottom tabs over bolts