14
WFS 1545 Operations Manual
The unit has a small integral reservoir with a float switch. The Lift Station pump turns on when
the reservoir level triggers the float switch. It is normal for the lift station to cycle on and off
during normal operation.
WARNING!
•
Accidental contact with electrically live components can cause serious injury or death.
•
Use appropriate GFI circuit protection
4.
COMPONENTS
a.
PUMPS
The system has three pumps with the Internal Circulating Loop and a Process Loop each having their
own pump mounted on the main base. A third pump is built into the remote lift station. The system
is designed to provide a nominal 15 GPM (57 LPM) at 45 PSI (0.31 MPa)
The Internal Circulating pump pulls water from the Dirty Side of the reservoir and pumps it through a
cascade of three (3) filters, a chiller and returns the water back to the clean side of the reservoir.
The Process Loop pump pulls clean, refrigerated water from the Clean Side of the reservoir. Pumps it
through a final cascade of two filters (3 filters for the F6 variant) and then out to the process.
The Lift Station pump returns used water back to the Dirty Side of the reservoir.
Internal Recirculating Pump
Gould # 3HM04N05T6PBQE
Nominal performance
•
0.75 hp
•
15 gpm
•
40 psi